Trouble shooting, 1 trouble shooting according to warning indication – PowerWalker VFI 6000T LCD User Manual

Page 50

Advertising
background image

47

7. Trouble Shooting


If the UPS system does not operate correctly, first check the operating
information on the LCD display.
Please attempt to solve the problem using the table below. If the
problem still persists, consult your dealer.

7.1 Trouble Shooting According To Warning Indication

Problem Displayed

Possible cause

Remedy

Read EEPROM Error

UPS internal fault

Consult dealer.

Epo Active

EPO connector is
closed

Check the EPO connector
status

On Maintain Bypass

Maintain bypass

switch is open

Check the maintain bypass

switch status

IP softstart failed

UPS internal fault

Consult dealer

Site Wiring Fault

Phase and neutral

conductor at input of

UPS system are

reversed

Reverse mains power wiring.

Battery Disconnect

Battery pack is not

connected correctly

Do the battery test to confirm.

Check the battery bank is

connected to the UPS.

Check the battery breaker is

turn on.

Battery low

Battery voltage is low

When audible alarm sounding

every second, battery is almost

empty.

Output Overload

Overload

Check the loads and remove

some non-critical loads.

Check if some loads are failed.

Fan Failure

Fan abnormal

Check if the fan is running

normally.

Charger Fail

The charge fails

Consult dealer.

Battery Over Voltage

Battery voltage is

higher than normal

value

Check if the battery quantity is

right.