6. Special Function

The series UPS has some special functions, which could satisfy
some special application of user. And the functions have own
features, please contact your local distributor for further information
before using the function.

6.1 HE Function

6.1.1 Brief introduction of HE function

If HE function is set to enable, after the UPS is turned on, the power

used by the load is directly supplied from the mains power via

internal filter while the utility power is in normal range, so the high

efficiency could be gained in HE mode. It is also called economy

mode. Once the mains power is loss or abnormal, the UPS would

transfer to Line mode or Battery mode and the load is supplied

continuously.

The great virtue is overall high efficiency

0.96 of UPS, to save

power for user.

But the disadvantage is 1) the load can not be protected as well as

in Line mode, for the load is directly supplied from the mains; 2) the

transfer time of UPS output from HE mode to Battery mode is about

10ms.

So the function is not suitable to some sensitive loads, and the

region where the mains power is unstable.

6.1.2 Set the function

The function could be enabled through the LCD setting in Bypass

mode.

Enter the power strategy setting menu by following chapter of 5.4.7.

Advertising