7.2 Trouble Shooting According To Fault Indication

Problem Displayed

Possible cause

Remedy

Inv Overload Fault

Overload

Check the loads and remove

some non-critical loads.

Check if some loads are failed.

Byp Overload Fault

Overload

Check the loads and remove

some non-critical loads.

Check if some loads are failed.

Output Short Circuit

Output short circuit

Remove all the loads. Turn off

the UPS.

Check if UPS output and loads

is short circuit.

Ensure short circuit is removed

before turning on again.

Heatsink Over

Temperature Fault

Inside temperature of

UPS is too high

Check the ventilation of UPS

and the ambient temperature.

Bus Over Voltage

UPS internal fault

Consult dealer.

Bus Under Voltage

UPS internal fault

Consult dealer.

Bus Unbalance

UPS internal fault

Consult dealer.

Bus short

UPS internal fault

Consult dealer.

Bus Softstart Fail

UPS internal fault

Consult dealer.

Inv Over Voltage

UPS internal fault

Consult dealer.

Inv Under Voltage

UPS internal fault

Consult dealer.

Inv Softstart Fail

UPS internal fault

Consult dealer.

Negative Power Fault

The load is pure inductive

and capacitive

Remove some non-critical

loads.

Bypass supplies the load first,

ensure there is no overload,

then turn on UPS.

Cable male and female

Loss fault

The parallel cable is

disconnected

Check the parallel cable.

Fan lock fault

Fan blocked or
disconnected over time

Check the fan status

Back Feed

Output voltage is
returned to input

Consult dealer