PowerWalker VFI 6000T LCD User Manual

Page 36

Advertising
background image

33

5.4.5 The control menu

By pressing

on the menu of “Control”, the display would enter

the next control menu tree.

1) Single UPS turn off: is one command to turn off one UPS which

is operated currently in a parallel system, and other UPSs

continue working to supply the load in the parallel system.

2) Single UPS battery test: is one command to control one UPS

which is operated currently in a parallel system to do the battery

test singly, and other UPSs do not do the battery test.

3) Parallel UPS battery test: is one command to control all UPS in

a parallel system to do the battery test at the same time.

4) Clear EPO status: once EPO status is enabled, the UPS output

would be cut off. To recover to normal status, first EPO

connector should be opened, and enter this menu to clear EPO

status, then UPS would stop alarm and recover to Bypass

model. And UPS needs be turned on by manual operation.

5) Reset fault status: when fault occurs, UPS would keep in Fault

mode and alarm. To recover to normal status, enter this menu

to reset error status, then UPS would stop alarm and recover to

Bypass mode. And the reason of fault should be checked and

deleted before UPS is turned on again by manual operation.

6) Restore factory settings: all the settings would be recover to

default factory settings. It could only be done in Bypass mode.