Table 5-4

Submenu item

Optional Values

Default value

User password

enabled/disabled

disabled

Audio alarm

enabled/disabled

enabled

Rated output voltage

208/220/230/240V

230V

Output frequency

autosensing/50/60Hz

autosensing

Power strategy**

normal/high efficiency/ converter normal

DC start

enabled/disabled

enabled

Site wiring fault alarm

enabled/disabled

enabled

Ambient

temperature

warning

enabled/disabled

enabled

Automatic

battery

tests

period

0-31days

7days

Auto Restart

enabled/disabled

enabled

Automatic overload restart

enabled/disabled

enabled

AutoBypass

enabled/disabled

enabled

Short circuit clearance

enabled/disabled

disabled

Bypass voltage low limit

110~215V

176V

Bypass voltage high limit

245~276V

264V

Bypass frequency low limit

1%~10%

10%

Bypass frequency high limit

1%~10%

10%

HE voltage low limit

1%~10%

5%

HE voltage high limit

1%~10%

5%

HE frequency low limit

1%~10%

5%

HE frequency high limit

1%~10%

5%

Battery quantity***

19/20/21

20

Set running time

Day:hour:minute:second
0000:0000:00~9999:23:59:59

Running time

LCD contrast

-5~+5

0

*Password is USER when enabled.

**Read the chapter of 6.1 and 6.2, before using high efficiency or converter function.

***Ensure the real battery quantity is same as the setting, or the batteries would be

damaged

permanently.