GE Industrial Solutions Neutral Mounting Kit - TNK100 User Manual

Neutral mounting kit, Ge consumer & industrial

Advertising
background image

g

DEH44149 Installation Instructions

Neutral mounting kit

1

Catalog number – TNK100

Introduction

This bulletin provides instructions for

installing Neutral lug kit – TNK100 on all

GE Double throw safety switch rated

100A & below

WARNING: Hazard of electrical shock or

burn. Turn off power before working

inside this equipment.

Description

This neutral kit consists of the following

parts on a plastic base:

1. One (1) Neutral assembly

2. Two (2) 8-32 X 3/8” mounting screws

3. One (1) Poly propylene insulators

4. One (1) Bond strap

5. One (1) 10-32 X 1/4” Slotted screw

Mounting Instruction

1. Tighten mounting screws in to

mounting hole in the enclosure ensuring

item 3 (insulator) beneath neutral asm.

Ref. Fig 1
2. Remove item A neutral screw qty 1 &

retain it. Ref. Fig 2

3. Insert item 4 (Bond strap) in neutral

assembly as shown in Fig 2 & install it

using item 5 screw.

4. Reinstall item A neutral screw on other

end removed in step 2.

Wire range: 12 – 1/0 CU/AL

Fig 1


Fig 2

g

These instructions do not purport to cover all details or variations in equipment nor to provide

for every possible contingency to be met in connection with installation operation or

maintenance. Should further information be desired or should particular problems arise which

are not covered sufficiently for the purchaser’s purposes, the matter should be referred to the GE

Company.


General Electric Company

GE Consumer & Industrial

41 Woodford Ave., Plainville, CT. 06062

DEH44149 R01 08/07 © 2007 General Electric

Visit us on the web at www.GEindustrial.com

Advertising