3f. Regulation card jumper settings

Jumper settings to use 6KCV300PIU PC Interface Unit - ( RS232 isolator )

Jumpers S18 & S19 = B, Jumper S29 & S30 = ON Jumper S15 = Off

or the 6KCV300CTI PC configurator Interface Unit - ( RS232/RS485 )

Jumpers S18 & S19 = B, Jumper S29 & S30 = On Jumper S15 = On

Jumper Factory

Description

Record

default

settings:

S4

Matching of the input voltage of the tachogenerator reaction, see table 4.4.3 (User manual)

Speed feedback channel selection

A = Enc 1 speed feedback channel

( XE1 connector with sinusoidal encoder, or digital encoder with 6KCV300DES )

B = analog tachometer

for digital encoder into XE2, or armature feedback (tachless) this jumper position has no effect

Analog input 1 setup

Off = 0-10 V/ -10 V to + 10 V input

ON = 4-20mA/0-20mA input

Analog input 2 setup

Off = 0-10 V/ -10 V to + 10 V input

ON = 4-20mA/0-20mA input

Analog input 3 setup

Off = 0-10 V/ -10 V to + 10 V input

ON = 4-20mA/0-20mA input

RS 485 programming port (XS) termination resistors

Off - no termination resistors

ON - termination resistors in

S15

On

Adaptation of the regulation card to the device type, see table 4.4.2 (User manual)

Selection of the internal/external supply of the RS485 serial interface

OFF - Serial interface supplied from the outside (PIN 5 and 9) and galvanic divided form the
regulation section.
ON - Serial interface supplied from the inside and connected to the potential reference point of the
regulation. PIN 5 and 9 are used to supply the adaptor of the serial interface (for use of
6KDV300PIU).

Encoder 2 input (XE2) marker channel ( also called index , or C channel) input

Off - marker channel (also called index , or C channel) input not used

ON - marker channel (also called index , or C channel) input monitored

Encoder 2 input (XE2) A, /A, B, /B voltage

Off - 15 ... 30 V

ON - 5 V

Tqs350

ON Mounted Jumpers

OFF Non mounted Jumpers

S21,S22,

S23

Off

S18,S19

B

S20

Off

S12,S13

Off

S10

Off

S11

Off

S5,S6

B

S9

Off

N

OTE

!

For sizes 6KDV3280... (American P/N) 6KDV3350... (European P/N) and higher, 115 VAC operation
requires a jumper between terminals SA & SB. These points are located on a terminal board on the top
of the converter module.