DV-300 Adjustable Speed Drives

—————— Quick Start up guide ——————

QS

31

Message

Possible causes

Hints

Enable seq error enable input circuit, TB 12, is closed

the enable input can not be tied to +24 V with

before the drive is finished powering up.

parameter [main commands = terminals] while the
drive powers up. This is to prevent unintentional
automatic restarting.

External fault

external fault circuit, TB point 15, is

control circuit is open

open circuit, not tied to +24 V

blown 24 V fuse

Overcurrent

overcurrent setting is too low

check parameter [ overcurrent thr ]

current regulator is mistuned

check Eint and regulator tuning

short circuit or ground fault in armature circuit

check motor circuit integrity

Field loss

no field current

blown fuse in field package AC input
field current parameters are wrong
open field circuit

field current below min field settings

check min field setting, field weakening
parameters
unstable flux regulator, check output current
stability and parameters [Flux P], [Flux I ],
[voltage P gain], [voltage I gain]

Speed fbk loss

loss of encoder input

check encoder power supplies, connections, and
wiring
check encoder jumper settings
misadjustment of encoder loss detection
misadjustment of [enable fbk contrl] parameters

Opt2 failure

DGF card failure

Option 2 is enabled with the DGF card ribbon
cable disconnected. Card is failed

DGF software error

A software error has occurred, for instance, a
divide by zero error.
Improper DGF card parameter settings have been
entered.
Reset the DGF card using jumper S17, also trying
cycling power.

Bus loss

Problem with the bus wiring

check wiring, termination resistors, etc...

excessive noise on the bus

check wiring, grounding practices

improper bus configuration

check bus info, data size, data type, addressing,
configuration data
replace card

Opt 1 failure

bad option 1 card

replace card