DV-300 Adjustable Speed Drives

—————— Quick Start up guide ——————

QS

15

5. INITIAL PARAMETER SETUP

This part of the procedure sets up the DV-300 for
CEMF feedback (open loop) with constant field
current.

The enable input and start input ( TB 12 and 13)
should be open circuit, i.e. not tied to 24 VDC.

GE DRIVE DV-300
DRIVE STATUS

Using the keypad, press the down arrow to go to the
START UP menu .

GE DRIVE DV-300
START UP

Press ENT

START UP
Speed base value

Press ENT

Enter the rated motor rpm recorded from section 3
d., ”gear in speed” corresponding to the maximum
desired motor rpm., press ENT

This parameter sets the value of speed reference that is
used as 100%, 1 per unit, in other words, the “base
value”.

Press the down arrow to go to the next parameter

START UP
Field curr scale

Press ENT

Enter the field current scale amps corresponding to
the S14 dipswitch setting recorded from section 3
e., press ENT

Press the down arrow to go to the next parameter.

START UP
Speed base value

Default = on,

Press the down arrow to go to the next parameter.

START UP
Acc delta speed

Press ENT

Enter the same rpm as entered for Speed base value
( rated machine motor rpm recorded from section
3 d., corresponding to the maximum desired motor
rpm ), press ENT

Press the down arrow to go to the next parameter.

START UP
Acc delta time

Press ENT

Enter the desired acceleration time in seconds as
recorded in section 3d., press enter

Press the down arrow to go to the next parameter.

START UP
Dec delta speed

Press ENT

Enter the same rpm as entered for speed base value(
rated motor rpm recorded from section 3 d.,
corresponding to the maximum desired motor rpm
), press enter

Press the down arrow to go to the next parameter.

START UP
Dec delta time

Press ENT

Enter the desired acceleration time in seconds as
recorded in section 3d., press enter

Press the down arrow to go to the next parameter menu.

START UP
Motor data

Press ENT

Motor data
Motor nom flux

Press ENT

Enter the nameplate base field current amps as
recorded in section 3d, press ENT

Press the down arrow to go to the next parameter.

Motor data
Flux reg mode

Press ENT

Use the + and - keys to select the desired flux
regulation control. The default setting = Constant
current = fixed field