EntelliGuard R Circuit Breaker Retrofill AKD-8 Installation Manual DEH-41549 02/12

AKD-8—Install Accessories

WIRING

Before installing the breaker, the

secondary disconnects must be wired

to the EntelliGuard Breaker.

Wires with wire markers are provided

on the retrofil. Make sure that the

switchgear wiring connection points

match up with the original wiring of the

cubicle. This ensures that all wiring

connections are properly made.

Wrong connections will cause the

breaker to malfunction.

AKD-8—Secondary Disconnects, Bullets

This section deals with installing and wiring the legacy secondary disconnect assemblies onto the Retrofill
EntelliGuard ACB. Installing the secondary disconnect assembly consists of doing these tasks:

• Installing the secondary disconnect assembly (bullets, shown in

Figure 15

, below)

• Wiring the secondary disconnect assembly (bullets, shown in

Figure 15

, below)

The Retrofill EntelliGuard ACB has these two options:

• All secondary disconnects installed

• No secondary disconnects installed

In case the application requires installing all 3 secondary disconnect blocks (actually, three sets of bullets),
you would select the first option. As secondary disconnects can be pre-installed on the breaker, wiring the
secondary disconnects can be done.

In case the application does not require any secondary disconnect assemblies, take the second option. Thus,
no further wiring is needed.

If the application requires less than 3 secondary disconnect blocks, the customer can choose the second
option, order the secondary disconnect blocks as needed, and then install the secondaries, completing the
wiring for the Retrofill EntelliGuard ACB. These options are discussed in the next sections.

Secondary Disconnect Assemblies

P/N 10105366G1

Retrofill Sec Disc Assy AKR

AKD8

P/N 10099265G2

FIXED SD ASSEMBLY

AKD8