EntelliGuard R Circuit Breaker Retrofill AKD-8 Installation Manual DEH-41549 02/12

Install AKD-8—Neutral Rogowski Current Transformer (CT)

Turn off all power to switchgear. Tagout

and lockout main source, up-stream or

main breaker.

Failure to comply with these instructions

will result in death or serious injury from

severe burns caused by arc flashing that

has exceedingly high temperatures.

Always wear personal protection

equipment according to OSHA standards

and appropriate to the severity of

potential burns.

Ensure only qualified personnel install, operate, service, and maintain all electrical

equipment.

AKD-8—Neutral Disconnect Assembly

SKUs

Breaker side

Compartment Side

Outline No

LCS Compt

Interface

AKR AKD8

P/N 10106054G1

10108266G1

139C5016

0343L0806G2

AKR30S

P/N 10107106G1

10108216G1

568B220

569B243-0020

Figure 32

shows an exploded view of the breaker side neutral disconnect assembly for the AKD-8

AKR30/30H/50/50H/30L and AKR30S Retrofillls. These are available pre-installed and wired from
the factory.

Figure 32. AKD-8—Neutral Disconnect Assembly for the AKR30H\50H Retrofill

AKD-8—Neutral Disconnect Assembly, Bus Compartment

The AKD-8 EntelliGuard R Circuit Breaker uses an air-core Rogowski Current sensor to measure current level
vs. an iron core CTs used in the legacy AK, AKR breakers. For the Retrofilll to calculate the current levels on
a 4-wire circuit, the Neutral Iron Core CT in the cable compartment needs to be replaced with a Rogowski
style CT.