EntelliGuard R Circuit Breaker Retrofill AKD-8 Installation Manual DEH-41549 02/12

2. Identify the type of programmer disconnect assemblies to be installed with retrofit kit.

The programmer disconnect assembly to be assembled depends upon the type of breaker the retrofil is
replacing. These are as follows:

• AKR30/30H/50/50H/30L—In these, the programmer disconnect is mounted on the left side wall of the

retrofil.

• AKR30S—In these, the programmer disconnect is mounted on the right side wall of the retrofil.

Programmer disconnect assemblies are available in two configurations for the Retrofill EntelliGuard ACB,
namely:

• 12-pin configuration—If the legacy LVS has a 12-pin programmer disconnect in use, the same can be

used with the Retrofill EntelliGuard ACB. In this case, only the breaker side programmer disconnect
assembly on the breaker needs to be installed. The numbers for the programmer disconnects are
mentioned below.

12-Pin Programmer Disconnect Breaker Side

P/N 10105385G1

PROG.DIS.ASSY, AKD8

AKR30H/ 50H AKD8

P/N 10105651G1

PROG. DIS. ASSY

AKR30S

19-Pin Programmer Disconnect Breaker Side

P/N 10108733G1

PROG.DIS.ASSY, AKD8

AKR30H/ 50H AKD8

P/N 10108732G1

PROG.DIS.ASSY, AKR30S

AKR30S

• 19-pin configuration—If the legacy LVS doesn’t have a 12-pin programmer disconnect configuration,

and the customer chooses to install a programmer disconnect, then the 19-pin programmer
disconnect assembly needs to be installed in the compartment and the breaker.

19-Pin Programmer Disconnect Breaker Side

10108733G1

PROG.DIS.ASSY, AKD8

AKR30H/ 50H AKD8

10108732G1

PROG.DIS.ASSY, AKR30S

AKR30S

19-Pin Programmer Disconnect Compartment Side

10108801G1

PROGRAMMER DISC ASSY

AKR30H/ 50H AKD8

10109176G1

PROGRAMMER DISC ASSY

AKR30S

3. If applicable, remove the existing compartment side programmer disconnect assembly.

The programmer disconnect assembly must be removed, if:

• A 9-pin programmer disconnect assembly is installed in the cabinet.

• A 24-pin programmer disconnect assembly is installed in the cabinet.

• Customer chooses to replace a 12-pin configuration with a 19-pin configuration.

4. Before uninstalling the existing programmer disconnect assembly, verify that the wiring details are

match the wiring numbers. Any changes or deviations need to be noted for use while installing the new
programmer disconnect.

5. Check that the compartment is de-energized and is safe to work in; and that the original or legacy

breaker has been removed form the cabinet.

6. Disconnect the wires connecting the terminal block to the compartment programmer disconnect

assembly. See