EntelliGuard R Circuit Breaker Retrofill AKD-8 Installation Manual DEH-41549 02/12

AKD-8—Programmer Disconnects

WIRING

Before installing the breaker, the

secondary disconnects must be wired

to the EntelliGuard Breaker.

Wires with wire markers are provided

on the retrofil. Make sure that the

switchgear wiring connection points

match up with the original wiring of the

cubicle. This ensures that all wiring

connections are properly made.

Wrong connections will cause the

breaker to malfunction.

The programmer disconnect consists of 2 assemblies, one mounted on the breaker side and the other
mounted on the cabinet. The breaker side assembly consists of the mounting bracket and plug assembly.
The compartment side assembly consists of the plug assembly mounted on a spring-loaded assembly that
receives the breaker.

WIRING

Note: Look for the wiring connection

scheme on the existing or old terminal

block and use the same references or

wiring info while re-wiring the new

terminal block..

Procedures
1.
Identify the existing programmer disconnect assemblies in the compartment.

The existing programmer disconnect plugs used in AKD-8 generation of the AKR breakers are provided
on the right side for the AKR30/30H/50/50H/30L and on the left side for the AKR30S retrofits.

Programmer disconnects are provided with legacy AKR breakers in AKD-8 LVS. The breakers were
equipped with the following pin configurations, depending on the application:

• 9-pin configuration

• 12-pin configuration

• 24-pin configuration