Installing the Phase Sensors (All Models)

1. Slide the CT spacer over each load-side copper

stab of the breaker, as illustrated in Figure 23.

2. Slide the phase sensors over each of the load-

side copper stabs. Be sure that each CT’s wire

leads are facing toward the front of the breaker

and are fed through the pole assembly under the

moving contact mounting plate, as shown in

Figure 24.

3. Mount the CT retaining plate to each phase base

molding using the two #10-32 x

1

/

2

" screws, lock

washers, and flat washers provided, as shown in

Figure 25. Be sure that the alignment stud on the

phase sensor inserts into the mating hole on the

CT retaining plate.

WARNING: In order to ensure the proper operation

of the phase sensors, it is crucial that the alignment
stud on each phase sensor aligns with the hole in
the CT retaining plate. Failure to properly install the
CTs may result in inadequate protection from the
trip unit.

4. Reattach the load-side draw-out primary contact

finger assemblies to the breaker using the pro-

vided X washers, as shown in Figure 16.

Figure 23. Installing the CT spacers.

Figure 24. Installing the phase sensors.

Figure 25. Installing the CT retaining plates.