GE Industrial Solutions MicroVersaTrip Plus and MicroVersaTrip PM AK-1-15, AK-1-25 User Manual
Page 6
6
3. Remove the nine mounting screws securing the
auxiliary switch mounting plate to the breaker, as
shown in Figure 4. Remove the mounting plate.
CAUTION: If the breaker contains auxiliary switches,
the auxiliary switch mounting plate must be
temporarily supported to the side in order to
prevent accidental damage to the breaker’s integral
wiring harness.
4. Remove the two retaining clips securing the
phase barrier support rod, then slide the rod out
through the side frame of the breaker, as shown
in Figure 5. Retain the rod and clips.
5. Loosen the locking bolt on the jack shaft of the
main contact closing arm, as shown in Figure 6.
Remove the adjustment screw from the clevis, as
shown in Figure 7.
Figure 4. Auxiliary switch mounting plate removal.
Figure 5. Removing the phase barrier support rod.
Figure 6. Loosening the locking bolt on the main contact closing
arm jack shaft.
Figure 7. Removing the adjusting screw from the jack shaft
clevis.