3. Remove the nine mounting screws securing the

auxiliary switch mounting plate to the breaker, as

shown in Figure 4. Remove the mounting plate.

CAUTION: If the breaker contains auxiliary switches,

the auxiliary switch mounting plate must be
temporarily supported to the side in order to
prevent accidental damage to the breaker’s integral
wiring harness.

4. Remove the two retaining clips securing the

phase barrier support rod, then slide the rod out

through the side frame of the breaker, as shown

in Figure 5. Retain the rod and clips.

5. Loosen the locking bolt on the jack shaft of the

main contact closing arm, as shown in Figure 6.

Remove the adjustment screw from the clevis, as

shown in Figure 7.

Figure 4. Auxiliary switch mounting plate removal.

Figure 5. Removing the phase barrier support rod.

Figure 6. Loosening the locking bolt on the main contact closing

arm jack shaft.

Figure 7. Removing the adjusting screw from the jack shaft

clevis.

Advertising