Adjusting the Flux Shifter

When the trip paddle and flux shifter have been
installed, the following adjustments must be made:

1. With the breaker in the CLOSED position, the gap

between the trip paddle and the flux shifter

adjustment screw, as shown in Figure 33, should

be approximately

1

/

16

". It may be helpful to

gauge the air gap with a

1

/

16

"-diameter rod (not

provided with the conversion kit). Make any

adjustments with the breaker OPEN, then CLOSE

the breaker and recheck the gap.

WARNING: Extreme caution must be used when

working on a CLOSED breaker. Do not reach your
hands into the breaker’s operating mechanism or
contact area while adjusting the flux shifter. Failure
to adhere to these precautions may result in serious
personal injury.

2. Optional Test – The flux shifter assembly may be

tested by closing the breaker and applying a 9

Vdc power source to the flux shifter leads. The

red wire (pin #2) is the positive lead, while the

white wire (pin #1) is the negative lead, The

breaker should open.

CAUTION: The 9 Vdc power source should only be

applied momentarily. Prolonged application of the
dc power source can damage the flux shifter.

Figure 33. Adjusting the flux shifter, viewed from the top of the

breaker.

Trip

Paddle

Adjustment

Screw

Gap

Advertising