9. The stationary and moving contact assemblies

must be separated from the original molded base

assembly. Remove the eight hex-head mounting

bolts, as shown in Figure 11. Retain the four

mounting bolts from the stationary contact

assembly. Discard the four bolts for the moving

contact assembly and the original base molding

and electromechanical trip device. Figure 12

shows the disassembled pole unit.

10. If the existing insulating strips, shown in Figure

10, are made of fiber board, they must be

replaced. Remove and discard the old insulating

strips and replace with the new, slide-on

insulators provided in the kit.

Installing New Phase Base Moldings (K-

3000 and K-4000 only)

1. Mount the stationary contact assembly to the

new phase base molding provided using the

hardware removed earlier, as shown in Figure 14.

2. Attach the contact mounting plate to the moving

contact assembly with the two

5

/

16

-18 x

3

/

4

" flat-

head bolts provided, as shown in Figure 13. Prick

the contact mounting plate on either side of each

mounting bolt head with a center punch to lock

the mounting bolts in place. Repeat this step for

each phase of the breaker.

3. Install the moving contact assembly and mount-

ing plate on the phase base molding with the two

5

/

16

-18 x 1

3

/

4

" hex-head bolts, lock washers, and

flat washers provided, as shown in Figure 14.

Repeat this step for each phase of the breaker.

4. Attach the mounting plate to the phase base

molding with the two

5

/

16

-18 x 1

3

/

4

" hex-head

bolts, lock washers, flat washers, and hex nuts

provided, as shown in Figure 14. Repeat this step

for each phase of the breaker.

Figure 11. Removing the contact assembly mounting bolts.

Figure 12. Disassembled pole unit.

Figure 13. Installing the contact mounting plate.

Figure 14. Converted pole assembly.