3. When the communications and/or the neutral CT
wiring are installed, tie these leads to the front of
the breaker where they will be accessible in the
switchgear cubicle. The actual location is
dependent on the configuration of the switchgear
assembly and the location of the mating
equipment in the switchgear. The installation and
termination points of these components may be
determined by a field engineer. If either the
communications or neutral CT wiring are
installed, a caution label, illustrated in Figure 42,
should be mounted on the breaker and on the
compartment door as a warning to prevent
damage
A mounting plate is supplied with each conver-
sion kit for locating the communication connec-
tor of the wiring harness. When the communica-
tion and/or neutral CT wiring are not used, they
should be coiled and tied next to the trip unit
bracket, as shown in Figure 43.
Figure 42. Caution label to be applied to the breaker and
compartment door.
Figure 43. Unused communications and neutral CT wiring tied
off.