SMR2 Modbus User Manual

7

Test mode

-- RW

5 150/160
6 250/250

7 400/400

8 600/630

9 800/800

10 1200/1250

11 1600/1600
12 350

13 500


0007

Information Memory
Option Byte 1

Bitmappe
d 0 to

FFFFh

Normal
mode--- RO


___________


Test mode

--- RW

b0 Instantaneous
0

enabled

1 disabled

b1 Short Time

0

enabled

1

disabled

b2 Long Time
0

enabled

1

disabled

b3 Watchdog

0

enabled

1

disabled

b4 Zone Select Interlock
0

enabled

1

disabled

b5 50-60/400 Hz

Operation

0 50/60 Hz

1 400 Hz
b6 Thermal Watchdog

0 disabled

1-99 enabled

b7 Unused


0008

Software revision
number

0000 to
9999

RO

4 digit BCD

Normal

mode --- RO

0009

Product revision

number

0000 to

9999

Test mode

--- RW

4 digit BCD

0010

Max Number of
events stored

Always 8

RO

Unsigned Int


Dynamic Value Registers

Actual value registers start at 1000, read by Function

Code 04.All the dynamic value registers are 32-bit in

length. Hence, query of any variable results in two

Modbus register reads, each of 16-bit length. Even

numbered register holds upper-16 bits; Odd numbered

register holds lower –16 bits

Example: To find out Phase-A SOS, A Modbus query to
read 1002 and 1003 registers need to be sent to SMR2

by the master.

There are 32 bits in this data. The upper-16 bits would

appear in register 1002 and lower-16 bits in register

1003 as a part of the response.