Reg Contents Units/

Range

Type

R/W

Format

2000

Event Code – Event 1

0-256

RO

Unsigned int

2001 Hour

0

RO Unsigned

int

2002 Minute

0

RO Unsigned

int

2003 Second

0

RO Unsigned

int

2004 Milliseconds

0

RO Unsigned

int

2005

Event specific data 1

0 - 65535

RO

Unsigned int

2006

Event specific data 2

0 - 65535

RO

Unsigned int

2007

Event specific data 3

0 - 65535

RO

Unsigned int

2008

Event code – Event 2

0-256

RO

Unsigned int

2009 Hour

0

RO Unsigned

int

2010 Minute

0

RO Unsigned

int

2011 Second

0

RO Unsigned

int

14




If another event occurs before the master reads all the

existing events, the oldest event is lost, new event data

will be placed in the EVENT 8 register, and the older

event register contents are shifted. The total number of
events since the last reset will be kept counted at

register location 1000-1001. Events are read using

Function Code 04.

2012 Milliseconds

0

RO Unsigned

int

2013

Event specific data 1

0 - 65535

RO

Unsigned int

2014

Event specific data 2

0 - 65535

RO

Unsigned int

2015

Event specific data 3

0 - 65535

RO

Unsigned int

… …

… …

2056

Event code – Event 8

0-256

RO

Unsigned int

2057 Hour

0

RO Unsigned

int

2058 Minute

0

RO Unsigned

int

2059 Second

0

RO Unsigned

int

2060 Milliseconds

0

RO Unsigned

int

2061

Event specific data 1

0 - 65535

RO

Unsigned int

2062

Event specific data 2

0 - 65535

RO

Unsigned int

2063

Event specific data 3

0 - 65535

RO

Unsigned int



Advertising