Smr2 modbus user manual – GE Industrial Solutions Record Plus FG600 SMR2 Modbus User Manual

Page 13

Advertising
background image

SMR2 Modbus User Manual

10

Normal
mode - RO

3002

Seconds

0 - 59

Test mode

RW

Unsigned int
(Unused)

3003 Long

Time

Pickup

0-15

Normal

Mode--RO

_________


Test Mode

RW

Unsigned int

0 0.625

1 0.65

2 0.675

3 0.7
4 0.725

5 0.75

6 0.775

7 0.8

8 0.825

9 0.85
10 0.875

11 0.9

12 0.925

13 0.95

14 0.975

15 1.0

3004 Long

Time

delay

0-6

Normal

Mode--RO

_________


Test Mode

RW

Unsigned int

0 Line

1.25

1. Line

2.5

2. Line

5

3. Line

10

4. Motor

20

5. Motor

30

6.

3005

Short time pickup

0-9

Normal

Mode--RO

----------------------

Test Mode

RW

Unsigned int


3006

Short Time delay

0-9

Normal

Mode--RO


_________

Test Mode

RW

Value second I

2

T

0 40ms No

1 120ms No
2 210ms No

3 310ms No

4 420ms No

5 420ms Yes

6 310ms Yes

7 210ms Yes
8 120ms Yes

9 40ms Yes

3007

Ground Fault pickup

0-8 (in GF

module
0-9 (in GFA

module)

Normal

Mode--RO

_________

Test Mode

RW

Unsigned int

0 0.2X
1 0.3X
2 0.4X

3 0.5X
4 0.6X

5 0.7X
6 0.8X

7 0.9X
8 1.0X