Smr2 modbus user manual – GE Industrial Solutions Record Plus FG600 SMR2 Modbus User Manual
Page 13
SMR2 Modbus User Manual
10
Normal
mode - RO
3002
Seconds
0 - 59
Test mode
RW
Unsigned int
(Unused)
3003 Long
Time
Pickup
0-15
Normal
Mode--RO
_________
Test Mode
RW
Unsigned int
0 0.625
1 0.65
2 0.675
3 0.7
4 0.725
5 0.75
6 0.775
7 0.8
8 0.825
9 0.85
10 0.875
11 0.9
12 0.925
13 0.95
14 0.975
15 1.0
3004 Long
Time
delay
0-6
Normal
Mode--RO
_________
Test Mode
RW
Unsigned int
0 Line
1.25
1. Line
2.5
2. Line
5
3. Line
10
4. Motor
20
5. Motor
30
6.
3005
Short time pickup
0-9
Normal
Mode--RO
----------------------
Test Mode
RW
Unsigned int
3006
Short Time delay
0-9
Normal
Mode--RO
_________
Test Mode
RW
Value second I
2
T
0 40ms No
1 120ms No
2 210ms No
3 310ms No
4 420ms No
5 420ms Yes
6 310ms Yes
7 210ms Yes
8 120ms Yes
9 40ms Yes
3007
Ground Fault pickup
0-8 (in GF
module
0-9 (in GFA
module)
Normal
Mode--RO
_________
Test Mode
RW
Unsigned int
0 0.2X
1 0.3X
2 0.4X
3 0.5X
4 0.6X
5 0.7X
6 0.8X
7 0.9X
8 1.0X