SMR2 Modbus User Manual

11

9 GFA Reset (In GFA module

only)

3008

Ground Fault delay

0-9

Normal

Mode

RO

_________

Test Mode

RW

Value second I

2

T

0 40ms No

1 120ms No

2 210ms No
3 310ms No

4 420ms No

5 420ms Yes

6 310ms Yes

7 210ms Yes

8 120ms Yes
9 40ms Yes

3009 Inst.

Pickup

0-9

Normal

Mode--RO


_________

Test Mode

RW

Unsigned int

Refer to the table

Normal

Mode - RO

3010

Module Address

0 - 240

Test mode

RW

3011

Last Trip Data

Bitmap

0 - 255

Normal

Mode--RO

_________

Test Mode
RW

3012 Control

Byte

Bitmap

0-255

Normal

Mode--RO

_________
Test Mode

RW

3013 Protection

Multiplier 64-100 Normal

Mode --RO
_________

Test Mode

RW

64% 100%

3014

Neutral Protection

0-100

Normal
Mode

RO

_________

Test Mode

RW

0%, 50%, 100%

3015 Temperature

Limit

0-100

degree

C

Normal

Mode

RO

_________

Test Mode
RW

3016

Product Reject Code Key

0 - 65535

RO

3017

Rating Plug Serial Number

high

0-9999 RO

3018

Rating Plug Serial Number

low

0-9999 Normal

mode - RO