SMR2 Modbus User Manual

MODBUS ADDRESSES


The master device addresses a specific slave device by

placing the 8-bit slave address in the address field of the

message (RTU Mode). The address field of the

message frame contains two characters (in ASCII

mode), or 8 binary bits (in RTU Mode). Valid

addresses are from 1-247.
When the slave responds, it places its own address in

this field of its response to let the master know which

slave is responding.

MODBUS FUNCTIONS


The function code field of the message frame will

contain two characters (in ASCII mode), or 8 binary

bits (in RTU Mode) that tell the slave what kind of

action to take. Valid function codes are from 1-255, but

not all codes will apply to a module and some codes are

reserved for future use.

MODBUS DATA FIELD


The data field provides the slave with any additional

information required by the slave to complete the

action specified by the function code. The data is

formed from a multiple of character bytes (a pair of

ASCII characters in ASCII Mode), or a multiple of two

hex digits in RTU mode, in range 00H-FFH. The data

field typically includes register addresses; count values,

and written data. If no error occurs, the data field of a

response from a slave will return the requested data. If

an error occurs, the data field returns an exception

code that the master's application software can use to

determine the next action to take.

CRC Error Checking


RTU Mode message frames include an error checking

method that is based on a Cyclical Redundancy Check

(CRC). The error-checking field of a message frame

contains a 16-bit value (two 8-bit bytes) that contains

the result of a Cyclical Redundancy Check (CRC)

calculation performed on the message contents.


The checksum field lets the receiving device determine

if a packet is corrupted with transmission errors. In

Modbus RTU mode, a 16-bit Cyclic Redundancy Check

(CRC-16) is used. The sending device calculates a 16-

bit value, based on every byte in the packet, using the

CRC-16 algorithm. The calculated value is inserted in

the error check field.

The receiving device performs the calculation, without

the error check field; on the entire packet it receives.

The resulting value is compared to the error check

field.

Transmission errors occur when the calculated

checksum is not equal to the Checksum stored in the

incoming packet. The receiving device ignores a bad

packet.



Electrical Interface

The electrical interface is 2-wire RS485 where data flow
is bi-directional and half duplex. RS-485 lines from the

master device should be connected to a FAMECM

module, which is powered externally using a 19-29 VDC

power supply. Refer Figure 1 and 2.


The following wire types are recommended for network

wiring: Belden 3074F – Data Tray 600 V industrial
twinax 18 AWG (7X26); or Belden 9841 – 300 V

communication cable 24 AWG (7X32); or Alpha 6412 –

300 V Communication cable 24 AWG (7x32). Shielded

wire should always be used to minimize noise. Polarity

is important in RS485 communications and each '+'

terminal of every device must be connected together for
the system to communicate.

Figure1. Connection between ETU and FAMECM