16

Bit position in Bit map

Bit Position in Bitmap

Meaning

Event code (Hex)

0

0 No Remote Trip

1 Remote Trip

6

1

0 Aux Switch Open
1 Aux Switch Closed

C

2

0 No Low Trip Voltage Warning

1 Low Trip Voltage Warning

0E

3

0 No RAM Failure

1 RAM Failure

10

4

0 No ROM Failure
1 ROM Failure

11

5

0 No Rating Plug Missing

1 Rating Plug Missing

13

6

0 No Short Time Switch Change

1 Short Time Switch Change

14

7

0 No Long Time Switch Change
1 Long Time Switch Change

15

8

0 No Instant Switch change

1 Instant Switch change

16

9

0 No Module Switch/Type Change

1 Module Switch/Type Change

17

10

0 No Short Time Delay Switch Change
1 Short Time Delay Switch Change

18

11

0 No Long Time Delay Switch Change

1 Long Time Delay Switch Change

19

12

0 No Missing Module

1 Missing Module

12