Register map, Fixed value registers, Smr2 modbus user manual – GE Industrial Solutions Record Plus FG600 SMR2 Modbus User Manual

Page 9

Advertising
background image

SMR2 Modbus User Manual

2

Register Map


While modbus communication with Target

Communication Accessory module, all the registers are

read only registers. None of them can be written. But

while Modbus communication with Test Kit, most of

the Fixed value & Setpoint registers can be read as well

as written.

Fixed value registers start at 0000 and are read by

Function Code 03.

Actual value registers start at 1000 and are read by

Function Code 04.

Event registers start at 2000 and are read by Function

Code 04.

Setpoint registers start at 3000 and are read by Function

Code 03.

Writing to the Coil registers, implement supervisory

control through remote commands

All registers composed of 16 bit integers, values less

than 256 stored in lower byte

Fixed Value Registers

Fixed value registers address starts at 0000, read by

Function Code 03. Written with Function code 06/16

(decimal)

The data stored in these registers are the data stored

during trip unit optioning.


Register

address

Contents Range

Type

R/W

Format

Normal

mode –RO

0000 Product

Id

0-65535

Test mode
--- RW

Unsigned Int

Normal

mode -- RO

0001 ETU

Serial

Number

high

0-65535

Test mode --

- RW

Unsigned Int

Normal
mode --- RO

0002 ETU

Serial

Number

low

0-65535

Test mode

--- RW

Unsigned Int

Normal

mode --- RO

0003 ETU

Date

Code

high

0-9999

Test mode
--- RW

Unsigned Int

Normal

mode --- RO

0004

ETU Date Code low

0-9999

Test mode

--- RW

Unsigned Int

Normal
mode --- RO


0005

Frame Size

1 to 3

Test mode

--- RW

Unsigned Int
1 G400

2 G630

3 K

0006

Amp Rating

1 to 13

Normal

mode--- RO

Unsigned Int

1 7/7

2 25/25

3 60/63

4 125/125