SMR2 Modbus User Manual

8

LT Accumulators (A, B, C & N) give normalized values

and are typically max 1.25. Hence, they are multiplied

with 10,000 and sent out on Modbus for reading

purposes.

Reg. Contents

Range

Type

R/W

Format

1000-01

Number of pending

event

0 - 4294967295

RO

Unsigned Int

1002-03

SOS Current Phase A

0 - 4294967295

RO

Unsigned Int

1004-05

SOS Current Phase B

0 - 4294967295

RO

Unsigned Int

1006-07

SOS Current Phase C

0 - 4294967295

RO

Unsigned Int

1008-09

SOS Current Phase N

0 - 4294967295

RO

Unsigned Int

1010-11

LT Accumulator A*10

4

0 - 4294967295

RO

Unsigned Int

1012-13

LT Accumulator B*10

4

0 - 4294967295

RO

Unsigned Int

1014-15

LT Accumulator C*10

4

0 - 4294967295

RO

Unsigned Int

1016-17

LT Accumulator N*10

4

0 - 4294967295

RO

Unsigned Int

1018-19

ST Accumulator

0 - 4294967295

RO

Unsigned Int

1020-21

GF Accumulator

0 - 4294967295

RO

Unsigned Int

1022-23

PL Accumulator

0 - 4294967295

RO

Unsigned Int

1024-25 Breaker

Status

Note:

If system is in pickup

corresponding bit is set to

1.
Battery status 1 indicates

healthy battery.

ZSI active is set 1 when

ZSI is ACTIVE.

When breaker is open

AUXS1bit is set to 1.

Bitmapped 0 to
FFFFh

RO B0:

Unused

B1: ST Pickup

B2: GF Pickup

B3: PL Pickup

B4 (unused)

B5: LT 105 Pickup (PU >= 105)

B6: LT 95 Pickup (95 <= PU < 105)
B7: LT 75 Pickup (75 <= PU < 95)

B8: LT 60 Pickup (60 <= PU < 75)

B9: LM 1

B10: LM 2

B11: ZSI active

B12: Battery Status
B13: AUXS1

B14, B15 Unused

1026-27

Push-Button Status

0 - 1

RO

Unsigned Int

1 = Push button is pressed
0 = Push Button is released

1028-29 Measured

ETU

Temperature

0 - 100

RO

Unsigned Int

1030-31

ETU Trip Count

0-655350

RO

Unsigned int

1032-33

LT Trip Count

0-65535

RO

Unsigned int

1034-35

ST Trip Count

0-65535

RO

Unsigned int

1036-37 Instantaneous

Trip

Count

0-65535 RO

Unsigned

int

1038-39

GF Trip Count

0-65535

RO

Unsigned int

1040-41

PL Trip Count

0-65535

RO

Unsigned int

1042-43

Software Fault Trip

Count

0-65535 RO

Unsigned

int

1044-45

Remote Trip Count

0-65535

RO

Unsigned int

1046-47

RP Missing Trip Count 0-65535

RO

Unsigned int

1048-49

Flash Erased Count

0-65535

RO

Unsigned int

1050-51

No module Trip Count 0-65535

RO

Unsigned int

1052-53

Over temperature Trip

Count

0-65535 RO

Unsigned

int