GE Industrial Solutions EntelliGuard G Cluster Pliers User Manual

Entelliguard, Circuit breaker, Accessories

Advertising
background image

.

Clusters pliers:
This is a tool used to remove and install the

cluster assembly on the circuit breaker main
terminals. It consists of the two jaws and the
extended handle as shown in fig.A

Figure A Figure B

Catalog: GUNI

Removal of Cluster assembly using cluster
pliers:


1. Turn the breaker off and discharge the

closing springs by depressing the OFF and
ON buttons in the sequence OFF-ON-OFF.

Verify that the breaker OFF-ON indicator
shows OFF on a green background and
that the charge indicator shows
DISCHARGE on a white background. If
installing in a draw-out type breaker

remove breaker from adaptor (cassette)
before continuing.

2. The breaker should be safely isolated and

fully removed from the cassette/panel.

3. Hold & position the cluster plier jaws on

the cluster fingers of the cluster finger
assembly at the rear ends.

4. Press the extended handles of the cluster

pliers assembly such that the cluster
assembly becomes loose on the rear
terminals as shown in fig B.






DEH-41395 Installation Instructions

EntelliGuard

®

G

Circuit Breaker


Accessories



Cluster Pliers Assembly



WARNING: Before installing any accessories, turn

the breaker OFF, disconnect it from all voltage

sources, and discharge the closing spings.

AVERTISSEMENT: Avant d’installer tout accessoire,

mettre le disjoncteur en position OFF, le
déconnecter de toute tension d’alimentation , et

décharger les resorts d’armement




5.

Then gently slide outwards the cluster
assembly over the rear terminals for
inspection or replacement.




Installing Cluster assembly using cluster pliers:

1. Hold & position the cluster plier jaws on

the cluster fingers of the cluster finger
assembly at the rear ends

2. Press the extended handle of the cluster

plier assembly such that the cluster
assembly opens at the other end.

3. Slide the cluster assembly along with the

cluster pliers on to the rear terminals.

4. Then release the extended handles gently

so that the clusters properly seats on the
grooves of rear terminal

5. Assemble the breaker in the cassette


1