3-5. Programmable inputs and outputs

Programmable inputs and functions

3. Technical specifications

The ASTAT-IBP Plus functions such as soft stop, kick start, etc., can be enabled (ON) or disabled (OFF) and set in their dedicated parameters by
using the keypad. Most of these functions can be enabled or disabled remotely as well, through the programmable inputs I3 or I4 (terminals 3-57
and 4-57).

Soft Stop

Pump Control

Kick Start

Linear Ramp

Dual Motor

Remote Control

S x x x

C x x x

P x x x

D x x x

A x x x

X x x x

_ O F F

_

O N

_

I

3

_

I

4

Function

Parameter

Set Value

The function is permanently disabled

The function is permanently enabled

The status of the function depends upon I3 input

The status of the function depends upon I4 input

NOTE: One programmable input may enable or

disable more than one function

<Remarks>

Programmable relay outputs

The ASTAT-IBP Plus includes two programmable relays 1

r

and 3

r

(dry contacts). ASTAT terminals are 11-12-14 and 33-34.

These relays can be assigned to several functions, as shown below.

Relay 1r

Relay 3r

22

23

24

25

27

28

29

30

Fault

Detects ASTAT-IBP Plus fault status

Undervoltage (1)

Detects limit set in parameter UVxx

Overvoltage (1)

Detects limit set in parameter OVxx

RUN

Detects ASTAT-IBP Plus run status

Undercurrent

Detects limit set in parameter UCxx

Overcurrent

Detects limit set in parameter OCxx

Disabled

Disables the relay function

Future use

Relay N#

Parameter

1 r x x

3 r x x

Set Value

<Remarks>

3-5

More than one function can be enabled in the ASTAT-IBP Plus, either by the keypad or through the programmable inputs I3 and I4, but there are
some functions which may not work as expected during stopping, such as when they are simultaneously enabled. When two or more of the below
functions are simultaneously enabled, the priority is defined in the following table:

Linear Ramp (S, D=ON)

a

a

Soft Stop (S=ON)

a

b

Pump Control (S, C=ON)

a

b

Linear Ramp (S, D=ON)

Soft Stop (S=ON)

Pump Control (S,

C=ON)

a

The unit stops by Linear Ramp

b

The unit stops by Pump Control

Condition

Action

○○

○○○○

○○

○○○○

Relay 2r has a fixed value of 20 (terminals 23-24) for end of ramp (EOR) Bypass Control.
Note: (1) Monitors L1