Installation, 4. start-up, 5. troubleshooting – GE Industrial Solutions ASTAT-IBP Plus User Manual

Page 26

Advertising
background image

5-4. Start-up

- Make sure equipment wiring corresponds

to one of the recommended routing
diagrams or equivalent.

- If the motor has thermal protection sensor, remove the link between

terminals 5 and 6 prior to wiring the sensor.

- Make sure the control wire harness corre-

sponds to the control voltage used.

- Set the Motor/Unit ratio (N)

Factory setting

N 1 0 0

Factory setting

o N 2

oxxx ;

xx x

OFF = disabled (extermal overload relay must be used
C1/C2 =

IEC Class 10 or Class 20

N1/N2/N3 = Nema 10, 20 or 30

Factory setting

Soft stop

S ON/OFF/I3/I4

S OFF

Deceleration ramp time

d x x x

d _ 2 0

- Set stopping parameters as needed:

- Set overload trip curve as needed:

- Set parameter K to ON (ON = 69 +

)

- Set parameter W to ON

- Press

(parameter W is set to OFF automatically)

If you change the default configuration and
wish to keep it, remember to rewrite the
parameters in E2PROM as follows :
(See page 4-9 for details)

- Send run command to equipment and make sure that operation is correct.

5. Installation

Display OFF

Symptom or Error & (Error Code)

Possible Cause

Measures to be taken

Check wire harness and control voltage

No control voltage
Main breaker tripped or fuse blown

F1 fuse blown on power supply PCB

Check and change, page 6-12

Verify connectors

Bad connection of flat ribbon wire joining
power supply PCB to control PCB

F2 fuse blown on power supply PCB

Check and change, page 6-12

Equipment does not respond to
STOP / START controls

5-5. Troubleshooting

5-3

Check power supply board and logic board
for 5VDC. Use a DC voltmeter on the
power supply board, (-) lead of voltmeter
on the top lead of C6 (located next to the
black heatsink on the right edge of the
power supply board) and the (+) lead of
voltmeter on top lead of Diode AD21 or
R25 (located on the upper right corner of
the power supply board.)

N x x x ; x x x =

In

Ir

x 100

Factory setting

Starting torque

T _ x x

T _ 2 5

Acceleration ramp time

a x x x

a _ 1 5

Kickstart

P ON/OFF/I3/I4

P OFF

Kickstart time

p x x x (if P enabled)

p 0 0 0

Current limit

L x x x

L 4 0 0

- Set starting parameters as needed:
L x x x = 450/N

L x x x =

Im

In

x 100

1. Enter the motor nameplate full load amperes: (In)

________

2. Enter the ASTAT-IBP Plus nameplate full load amperes: (Ir)

________

3. Divide Line 1 by Line 2 and multiply by 100. This is your N parameter value.

________

4. Enter the facility or installation maximum allowable amperes:

________

5. Divide Line 4 by Line 1 and multiply by 100. This is your maximum allowable
L parameter value governed by facility limitations.

________

6. Divide 450 by Line 3 and multiply by 100. If the result is greater than 450, enter 450.
This is you maximum allowable L parameter value governed by ASTAT-IBP Plus limitations. __________
7. Enter the value of Line 5 or Line 6, whichever is lower. This is your maximum
allowable L parameter value.

________

Advertising