Maximum Horsepower

kW

Number

Rating, A

200 V

230 V

460 V

575 V

220 V

380 V/

440 V

480 V/

415 V

500 V

QI3KDP

55

15

20

40

50

17

30

37

40

QI3LDP

68

20

25

50

60

20

37

40

45

QI3YDP

80

25

25

60

75

22

37

45

50

QI3MDP

105

30

40

75

75

30

55

63

75

QI3ZDP

130

40

50

100

125

37

63

75

80

QI3NDP

156

50

60

125

150

40

75

80

90

QI3PDP

192

60

75

150

200

55

90

100

110

QI3QDP

248

75

100

200

250

63

110

132

147

QI3RDP

302

100

100

250

300

90

160

185

220

QI3SDP

361

125

150

300

350

110

200

220

250

2. Types and Ratings

2-1

2-1. Ratings

(1)

Notes:

(1) = Ratings in Amps given for ambient temperature of up to 40

°

C and 1000m altitude. Temperatures inside the

enclosure must be kept within a 0

°

-45

°

C range. Derate output current by 1.5% per degree C above 40

°

C. Derate

output current by 1% per 100m above 1000m.

Ratings for Standard Duty Applications (300% Current for 30 sec) for low inertia loads such as centrifugal pumps.

Catalog

Frame

Maximum Horsepower

kW

Number

Rating, A

200 V

230 V

460 V

575 V

220 V

380 V/

440 V

480 V/

415 V

500 V

QI3KDP,LP,YP

55

15

20

40

50

17

30

37

40

QI3MDP

105

30

30

75

75

22

50

63

63

QI3ZDP

130

40

50

100

125

37

63

75

80

QI3NDP

156

50

60

125

150

40

75

80

90

QI3PDP,QP,RP

192

60

75

150

200

50

90

100

110

QI3SDP

361

75

100

200

250

63

110

132

132

Ratings for Heavy Duty Applications (450% Current for 30 sec) for medium loads such as belted conveyors.