Technical specifications, 1. astat, Ibp plus, general specifications – GE Industrial Solutions ASTAT-IBP Plus User Manual

Page 9

Advertising
background image

Voltage Ratings 3ph AC Systems

Up to 600V, +10%, -15% for QI3xDP ASTAT-IBP
Plus series

Freq. Range

50/60

Hz

Control range of 45-65 Hz

Control

Control system

Digital system with microcontroller

Specifications

Starting ramp with progressive increase in voltage and
current limitation

Initial voltage (pedestal)

%

30 - 95 Un

Starting torque

%

10 - 90 Mdirect start

Kick start

%

95 Un (90% Mdirect start), adjustable 0 to 999 ms

Motor unit ratio (N)

0.4 - 1.2

Current limit (starting)

1 to 4.5 (Ir/In) Max 4.5 In

Acceleration ramp time

s

1 to 45 (standard or linear ramp up)

Bypass

Direct control of a bypass contactor

Brake time by ramp

s

1 to 60 (1 to 60 in secondary ramp) adjustable independently of starting
ramp time (types: standard, pump control or linear ramp down)

Monitoring

Motor current, line voltage (1), power, power factor and elapsed time

Running

External control

Start - Stop

Acceleration phase

Adjustable time

Stop phase

Power cut-off / Ramp / Pump control

Inputs / Outputs Inputs

4 digital optocoupled. Two fixed (Start , Stop), and 2 programmable (I3, I4)
1 Analog 0-5VDC for Tachogenerator input feedback

Outputs

2 Programmable relays (1r, 3r); 1 fixed relay (2r)
1 Analog 0-10VDC output for current metering

Protections

Current limit

Adjustable 1 to 4.5 (Ir

/

In) Max 4.5 In

Overload

IEC class 10 and 20 ; NEMA class 10, 20 and 30 all selectable

Cool-down time after
overload trip

See Restart Times on page 4-10

Loss on input phase

s

Trip at 3

Thyristor short circuit

ms

Trip at 200

Heatsink overheating

ms

Trip at 200

Motor thermistor

ms

Trip at 200 if thermistor impedance > response value

Loss on output phase

s

Trip at 3

Stalled rotor

ms

Trip at 200

Supply frequency error

Hz

If f < 45 or f > 65, will not start

Overcurrent

100 to 150% In; trip time adjustable from 0 to 99 sec.

Undercurrent

0 to 99% In; trip time adjustable from 0 to 99 sec.

Overvoltage (1)

100 to 130% Un; trip time adjustable from 0 to 99 sec.

Undervoltage (1)

0 to 50% Un; trip time adjustable from 0 to 99 sec.

Error (CPU)

ms

60

Memory

4 former errors

Long start time

s

2 x ta (ta = acceleration ramp time)

Environmental

Temperature

°C

0 to +55 (derate output current by 1.5% /

°C above 40°C)

conditions

Relative humidity

%

95% without condensation

Maximum altitude

m

3000 (derate output current by 1% / 100m above 1000m)

Mounting position

Vertical

Protection Degree

IP00, UL Open

Standards

cUL, UL

UL, cUL conforming to UL508

Conducted & radiated emissions

Conforming IEC 947 -4-2, Class A

Electrostatic discharges

Conforming to IEC 1000-4-2, level 3

Radioelectric interference

Conforming to IEC 1000-4-6, level 3 and to IEC 1000-4-3, level 3

Immunity to fast trasients

Conforming to IEC 1000-4-4, level 3

Immunity to Surge Voltage

Conforming to IEC 1000-4-5, level 3

3-1. ASTAT

®

-IBP Plus, General specifications

3. Technical Specifications

3-1

(

I

Actual measured motor current

Im

Maximum starting current desired

In

Nominal motor nameplate FLA

Ir

ASTAT rated nameplate FLA

L

Current limit for starting Im/Ir

Lmax

450/N

Mdirect start Full voltage starting torque
N

In/Ir

SF

Service factor

Un

Full line voltage

Note: (1) Monitors L1

Abbreviations

Advertising