Programming, 7. application and basic settings – GE Industrial Solutions ASTAT-IBP Plus User Manual

Page 21

Advertising
background image

Function

Display

Description

Default

Range

4-6-3. Relay output functions

Output relay 1r

Output relay 2r

Output relay 3r

1 r x x

2 r x x

3 r x x

1 r 2 5
(RUN)

2 r 2 0
(EOR)

3 r 2 2

This is a programmable relay with one NO / NC dry contact to
ASTAT-IBP Plus terminals 11-12-14.

This is a non-programmable relay with one NO dry contact to
ASTAT-IBP Plus terminals 23-24.
This relay is assigned to by-pass control.

This is a programmable relay with one NO dry contact to ASTAT-
IBP Plus's terminals 33-34.

22-30

20

22-30

The programmable relays can be set to the functions shown in the following table:

Function

EOR
FAULT
Undervoltage
Overvoltage
RUN
Undercurrent
Overcurrent
Disabled
Future use

Remarks

Detects end of voltage ramp. This function may only be assigned to relay 2r-
Detects unit Fault status. ON is normal status and switches OFF if a fault occurs
Detects Undervoltage according limit adjusted in function “UV”
Detects Overvoltage according limit adjusted in function “OV”
Detects unit RUN status
Detects Undercurrent according limit adjusted in function “UC”
Detects Overcurrent limits as adjusted in function “OC”
Disables the relay function

Range

20
22
23
24
25
27
28
29
30

4. Programming

4-8

Display

Parameter

Parameters (1)

Factory

Default

4-7. Application and basic settings

Nominal motor current

N x x x

100

Current limit

L x x x

400

375

400

Initial torque

T x x x

025

030

035

020

020

Acceleration ramp time

a x x x

015

015

030

030

015

Deceleration ramp time

d x x x

020

040

Kick start time(2)

p x x x

000

100

Soft stop

S x x x

OFF

ON

Pump control

C x x x

OFF

ON

Pump curve starting

S T x x

02

02

Pump curve stopping

S P x x

02

02

Kick start

P x x x

OFF

ON

Overload trip curve(3)

o x x x

ooN2

ooN2

ooN2

ooC2

ooC1

ooC1

Service Factor(3)

f x x x

100

Compressor

Mill

Fan

Machine

Tool

Pump

Control

Settings (X X X)

Different applications will require different characteristics and settings for the ASTAT-IBP Plus. The table below lists typical settings for
various applications.

Notes:

(1) = GBAS Block Parameters unless noted(2)(3)

(2) = Parameter “p” is disabled while “C” is ON.
(3) = GCAL Block Parameters