J85568E-1 Secondary DC Mini-Distribution Bay

5 - 10 Installation

Issue 6 January 2008

If wiring for Open on Alarm (AUD, VIS, or REMOTE), strap
across the common and normally closed contacts in the empty
fuse panel positions of the 847206737 PWB assembly on the
rear of the alarm and meter panel. For example, if fuse panels are
located in positions 1 and 3 with blank panels in positions 2 and
4, then:

Fuse or circuit breaker Alarm (Audible):

Strap from P202

position 4 to

P202 position 5

Strap from P204

position 4 to

P204 position 5

Fuse or circuit breaker Alarm (Visual):

Strap from P202

position 7 to

P202 position 8

Strap from P204

position 7 to

P204 position 8

Fuse Alarm or circuit breaker (Remote):

Strap from P202

position 10 to

P202 position 11

Strap from P204

position 10 to

P204 position 11

If wiring for Open on Alarm (POWER LOSS), strap across the
common and normally open contacts in the first empty fuse or
circuit breaker panel position only. From the example above:

Power Loss:

Strap from P202

position 1 to

P202 position 3