Figure 5-6: alarm termination board, For generating frame alarms – GE Industrial Solutions Micro-BDCBB User Manual

Page 39

Advertising
background image

Table 5-A: DIP Switch Settings and Alarm Connections

for Generating Frame Alarms

Closure on Alarm (FAJ: C and NO Contacts; PWR Loss: C and NC Contacts)

Alarm Type

DIP Switch Setting

Alarm

Connection

P201

P204

Power Loss

Fuse or Circuit Breaker Alarm (Audible)

Fuse or Circuit Breaker Alarm (Visual)

Fuse or Circuit Breaker Alarm (Remote)

Close Positions 1 and 2 on SW1, SW3, and SW5

Close Positions 4 and 6 on SW1, SW3, and SW5

Close Positions 1 and 3 on SW2, SW4, and SW6

Close Positions 4 and 6 on SW2, SW4, and SW6

pin 1

pin 4

pin 7

pin 10

pin 2

pin 6

pin 9

pin 12

Open on Alarm (FAJ: C and NC Contacts; PWR Loss: C and NO Contacts)

Alarm Type

DIP Switch Setting

Alarm

Connection

P201

P204

Power Loss

Fuse or Circuit Breaker Alarm (Audible)

Fuse or Circuit Breaker Alarm (Visual)

Fuse or Circuit Breaker Alarm (Remote)

Close Position 3 on SW1, SW3, and SW5

Close Position 5 on SW1, SW3, and SW5

Close Position 2 on SW2, SW4, and SW6

Close Position 5 on SW2, SW4, and SW6

pin 1

pin 4

pin 7

pin 10

pin 3

pin 5

pin 8

pin 11

Figure 5-6: Alarm Termination Board

J85568E-1 Secondary DC Mini-Distribution Bay

Issue 6 January 2008

Installation 5 - 11