TVRMS2 Digital Test Kit

Chapter 3. Initialization and Setup

7

3–4 Test Selection Sequence

After the Trip Unit type has been selected, the Test Kit
verifies that a Trip Unit is connected through the
communication link. If no Trip Unit is connected, the
following message appears:

Digital Link Open; Check Connection

|– MORE –|

Display indicating that Trip Unit is not connected.

A Trip Unit must be properly connected before the test
sequence can continue. When this has been done, press

MORE

(

F1

) to return to the main Trip Unit selection menu.

If the Trip Unit is properly connected, the Test Kit displays
the main test-selection menu:

. . ... . . ... . .. .. .. ..... .

Press F1,F2, or F3 for test selection

|FUNCTION |HICURRENT| QUICK |

Main test-selection menu.

If the following message appears while any test is being
run, press

MORE

(

F1

) to restart the test.

. .. ..

Program interrupted; restart test

|- MORE -|

Message indicating that test should be restarted.

If a TS-type (RMS-9, Power+, or Epic) Trip Unit is to be
tested, see Chapter 4 for detailed instructions.

If a TT-, A-, B-, or C-type (MicroVersaTrip Plus or
MicroVersaTrip PM) or Spectra (MicroVersaTrip Plus or
MicroVersaTrip PM in a Spectra RMS molded-case circuit
breaker) Trip Unit is to be tested, see Chapter 5 for
detailed instructions.