4–4 overcurrent simulation, Long time test, Short time test – GE Industrial Solutions TVRMS2 Digital Test Kit User Manual

Page 18: Ground fault test, Overcurrent simulation test

Advertising
background image

TVRMS2 Digital Test Kit
Chapter 4. Power+™, RMS-9, and Epic Trip Units

12

Press the

MORE

(

F3

) key after the last failure message to

return to the Trip Unit test menu, or

EXIT

(F4

) to return

to function test menu.

In the event of any subunit failure, remove the breaker
from service and refer the Trip Unit to an authorized GE
service representative.

4–4 Overcurrent Simulation

The Test Kit can simulate a time-overcurrent condition for
each of the following fault types:

• Long Time fault
• Short Time fault
• Ground Fault

The Test Kit first determines whether or not the breaker is
to be allowed to trip with the message:

... ..... ..... ..... ..... ..... ..... ..... ...

Do you want the breaker to trip?

|– YES –| |– NO –|– EXIT –|

Trip query display.

If

YES

(

F1

) is selected, the

TRIP TEST

LED begins to flash.

If

NO

(

F3

) is selected, the

NO TRIP TEST

LED activates. The

next menu lists the available tests:

... ..... ..... ..... ..... ..... ..... ..... .....

Select Test (F4 to EXIT)

|– LT –|– ST –|– GF –|– EXIT –|

Overcurrent test selection menu.

If

ST

(

F2

) or

GF

(

F3

) is selected, the Test Kit first verifies

that the option is installed in the Trip Unit. If that option
is not installed, the appropriate message is displayed, as
illustrated above in the Short Time and Ground Fault
settings tests.

Long Time Test

If

LT

(

F1

) is selected, the Test Kit displays the message:

... ..... ..... ..... ..... ..... ..... ..... ..... ..

Set Current Setting and press F3

|– CONT –|– EXIT –|

Long Time current setting display.

Select the desired current setting on the Trip Unit, then
press

CONT

(

F3

), which displays the verification message:

... ..... ..... ..... ..... ..... ..... ..... ..... ....

LONG TIME TEST WITHOUT BREAKER TRIP

|– CONT –|– EXIT –|

Long Time test verification display.

Press

CONT

(

F3

) to initiate the test or

EXIT

(

F4

) to return

to the function test menu.

Short Time Test

If

ST

(

F2

) is selected from the overcurrent test selection

menu, the Test Kit displays the message:

... ..... ..... ..... ..... ..... ..... ..... ..... ..... .

Set Short Time Pickup and press F3

|– CONT –|– EXIT –|

Short Time Pickup setting display.

Select the desired Short Time Pickup setting on the Trip
Unit, then press

CONT

(

F3

), which displays the verification

message:

... ..... ..... ..... ..... ..... ..... ..... ..... ..... ...

SHORT TIME TEST WITHOUT BREAKER TRIP

|– CONT –|– EXIT –|

Short Time test verification display.

Press

CONT

(

F3

) to initiate the test or

EXIT

(

F4

) to return

to the function test menu.

Ground Fault Test

If

GF

(

F3

) is selected from the overcurrent test selection

menu, the Test Kit displays the message:

... ..... ..... ..... ..... ..... ..... ..... ..... ..... .....

Set Ground Fault Pickup and press F3

|– CONT –|– EXIT –|

Ground Fault Pickup setting display.

Select the desired Ground Fault Pickup setting on the Trip
Unit, then press

CONT

(

F3

), which displays the verification

message:

... ..... ..... ..... ..... ..... ..... ..... ..... ..... ..... ..

GND FAULT TEST WITHOUT BREAKER TRIP

|– CONT –|– EXIT –|

Ground Fault test verification display.

Overcurrent Simulation Test

During the simulation for any of the three types of test, the
Test Kit first ramps up the simulation current, starting
from less than .9 times the pickup current and continuing
until pickup is reached. At that point, the display contains
the message:

... ..... ..... ..... ..... ..... ..... ..... ..... ..... ..... ....

Input Current = 1.00C IN PICKUP

<Press any key to test at current shown>

Overcurrent simulation pickup display.