Pm trip units, 5–2 pickup settings, 5–3 self-test report – GE Industrial Solutions TVRMS2 Digital Test Kit User Manual

Page 22: 5–4 overcurrent simulation

Advertising
background image

TVRMS2 Digital Test Kit
Chapter 5. MicroVersaTrip Plus™ and MicroVersaTrip

PM Trip Units

16

5–2 Pickup Settings

The Test Kit cannot be used to check the pickup settings
of MicroVersaTrip Plus and MicroVersaTrip PM Trip
Units.

NOTE: Settings of MicroVersaTrip Plus and Micro-
VersaTrip PM Trip Units should be verified at the Trip
Unit display.

The Trip Unit LCD always displays the

correct stored settings. The Test Kit is not designed to

read the settings of these Trip Units.

NOTE: Les réglages des MicroVersaTrip Plus et
MicroVersaTrip PM sont vérifiés sur l’écran des
déclencheurs.

Cet écran indique les réglages memorisés.

Ces valeurs ne peuvent pas être visualisées avec l’écran du
Test Kit.

5–3 Self-Test Report

Select

SELF TEST

(

F3

) from the Trip Unit tests menu to

initiate the Trip Unit self-test. The test verifies the
operation of the following:

• Analog-to-digital converter
• Read-only memory (ROM)
• Random-access memory (RAM)
• Nonvolatile memory

If all modules pass the self-test, the following message is
displayed:

Trip Unit is OK

|– MORE –|– EXIT –|

Trip Unit self-test display.

Press the

MORE

(

F3

) key to return to the Trip Unit test

menu or

EXIT

(

F4

) to return to the function test menu.

If the Trip Unit fails the self-test, a failure message is
displayed for each of the subunits that failed. If more than
one subunit failed, press the

MORE

(

F3

) key to display them

all. The failure messages are displayed as follows:

... ..... ..... ..... ..... ..... .....

A/D Converter Failed

|– MORE –|– EXIT –|

A/D converter failure message.

... ..... ..... ..... ..... ..... ..... ..

RAM Failed

|– MORE –|– EXIT –|

RAM failure message.

... ..... ..... ..... ..... ..... ..... ....

ROM Failed

|– MORE –|– EXIT –|

ROM failure message.

... ..... ..... ..... ..... ..... ..... ..... .

Non-volatile Memory Failed

|– MORE –|– EXIT –|

Nonvolatile memory failure message.

Press the

MORE

(

F3

) key after the last failure message to

return to the Trip Unit test menu, or

EXIT

(F4

) to return

to function test menu.

In the event of any subunit failure, remove the breaker
from service and refer the Trip Unit to an authorized GE
service representative.

5–4 Overcurrent Simulation

The Test Kit can simulate time-overcurrent conditions for
each of the following fault types:

• Long Time fault
• Short-time fault
• Ground fault

However, overcurrent simulations for MicroVersaTrip Plus
and MicroVersaTrip PM Trip Units may require that the
Long Time current, Short Time Pickup, and Ground Fault
Pickup settings be entered manually into the Test Kit. The
following sequence should be followed in order to perform
an overcurrent simulation with one of these Trip Units:

1. Connect the TVRMS2 Test Kit to the MicroVersaTrip

Plus or MicroVersaTrip PM Trip Unit and turn on
the Test Kit.

2. Select the Trip Unit on the appropriate Trip Unit

selection menu, then select

FUNCTION

(

F1

) from the

main test-selection menu and

TRIP TEST

(

F1

) from

the Trip Unit tests menu.

3. The Test Kit displays a Long Time Pickup value, as

shown:

... ..... ..... ..... ..... ..... ..... ..... ..... ..... ..... ..... ..... ..... ..... ..... ..... .....

.. .

LT Pickup .90X

|– MORE –|– VALUE –|– ENTER –|– EXIT –|

Long Time Pickup setting display #1.

In Setup mode on the Trip Unit, read the Long Time

Pickup setting from the Trip Unit display.

4. If the Long Time Pickup setting on the Test Kit

display does not match the value on the Trip Unit
display, press the

VALUE

(

F2

) key on the Test Kit until

the value displayed on the Test Kit matches the value
displayed on the Trip Unit.

Advertising