2–1 front panel, 2–2 top panel (test cable connection) – GE Industrial Solutions TVRMS2 Digital Test Kit User Manual

Page 9

Advertising
background image

TVRMS2 Digital Test Kit

Chapter 2. Controls, Indicators, and Connections

3

2–1 Front Panel

Figure 2 shows the front panel of the Test Kit.

Figure 2. Front panel of the Test Kit.

The functions of the various switches and displays on the
front panel are as follows:

Display Panel – The display panel is a 40-character by

2-line liquid crystal display (LCD). The top line
contains instructions and information for each stage
of the test. The bottom line identifies the functions of
each of the four function keys during each test.

Function Keys – The function of each of the keys is

determined by the test state of the Test Kit and is
identified on the bottom line of the display panel.
The function keys are labeled form left to right as

F1

,

F2

,

F3

, and

F4

.

LEDs – There are six light-emitting diodes (LEDs) on

the front panel:

FUNCTION TEST

– A yellow LED that lights when

the Test Kit is in the function test sequence.

HI CURRENT TEST

– A yellow LED that lights

when the Test Kit is in the High-Current test
sequence.

NO TRIP TEST

– A yellow LED that lights if the test

being performed will not trip the breaker.

BREAKER TRIPPED

– A red LED that flashes when

the Trip Unit under test has tripped the breaker.

TRIP TEST

– A red LED that flashes if the test

being performed will trip the breaker. This will
occur if

Quick Test

is selected or if

Trip Test

is

selected during an Overcurrent Test sequence.

LOW BATTERY

– A red LED that lights when the

Test Kit battery is becoming weak. Further testing

under low-battery conditions can yield erroneous
test results.

Escape Key – Pressing the

ESCAPE

key returns the Test

Kit to its power-up or “home” state and initiates the
self-test sequence.

On-Off Switch – The

ON-OFF

rocker switch has a red

band that is visible when the Test Kit is on.

Legend – The legend provides a quick reference to the

various abbreviations used on the display.

2–2 Top Panel (Test Cable Connection)

The top panel contains a test port,

Test Port A

, which

accepts the 3.5 mm, three-conductor plug attached to the
test cable. The other end of the test cable is inserted into
the test jack of the Trip Unit rating plug. A similar test
cable can be obtained from Radio Shack (catalog number
42-2387).

CAUTION: Switch the Test Kit power off before inserting
the test jack into or removing it from the Trip Unit rating
plug.

ATTENTION: Eteindre le Test Kit avant de connecter ou
de déconnecter la prise jack du calibreur.

Advertising