Long time test, Short time test – GE Industrial Solutions TVRMS2 Digital Test Kit User Manual

Page 23

Advertising
background image

TVRMS2 Digital Test Kit

Chapter 5. MicroVersaTrip Plus™ and MicroVersaTrip PM™ Trip Units

17

5. Press

ENTER

(

F3

) on the Test Kit to store the correct

Long Time Pickup value in the Test Kit.

6. Press

MORE

(

F1

) to display the next Long Time

Pickup setting display:

... ..... ..... ..... ..... ..... ..... ..... ..... ..... ..... ..... ..... ..... ..... ..... ..... .....

.. ...

LT Pickup .90X

|– NEXT –|– PREV –|– TEST –|– EXIT –|

Long Time Pickup setting display #2.

Select

PREV

(

F2

) to return to the previous display.

Select

NEXT

(

F1

) to display the Short Time Pickup

setting:

... ..... ..... ..... ..... ..... ..... ..... ..... ..... ..... ..... ..... ..... ..... ..... ..... .....

.. .... .

ST Pickup 3.00C

|– MORE –|– VALUE –|– ENTER –|– EXIT –|

Short Time Pickup setting display #1.

(If Short Time trip is not an option on the Trip Unit

under test, the next parameter displayed is Ground
Fault Pickup.)

7. In Setup mode on the Trip Unit, read the Short Time

Pickup setting from the Trip Unit display. If it does
not match the value shown on the Test Kit display,
press the

VALUE

(

F2

) key on the Test Kit until it

matches the Trip Unit setting.

8. Press the

ENTER

(

F3

) key on the Test Kit to store the

correct Short Time Pickup value in the Test Kit.

9. Press

MORE

(

F1

) to display the second Short Time

Pickup display:

.

ST Pickup 3.00C

|– NEXT –|– PREV –|– TEST –|– EXIT –|

Short Time Pickup setting display #2.

10. Press

NEXT

(

F1

) to move to the Ground Fault Pickup

value:

. .. ... .

GF Pickup 0.2S

|– MORE –|– VALUE –|– ENTER –|– EXIT –|

Ground Fault Pickup setting display #1.

11. In Setup mode on the Trip Unit, read the Ground

Fault Pickup setting from the Trip Unit display. If it
does not match the value shown on the Test Kit
display, press the

VALUE

(

F2

) key on the Test Kit until

it matches the Trip Unit setting.

12. Press

ENTER

(

F3

) to store the correct Ground Fault

Pickup value in the Test Kit.

13. Press

MORE

(

F1

) followed by

TEST

(

F3

) to initiate the

test sequence.

NOTE: Hitting the

EXIT

key at any time after entering

values will reset all set points to their default values.

NOTE: A tout moment, si vous appuyez sur le touche

EXIT

, les réglages sont réinitialisés avec les valeurs par

défaut.

The Test Kit first determines whether or not the breaker is
to be allowed to trip with the message:

... ..... ..... ..... ..... ..... ..... ..... ...

Do you want the breaker to trip?

|– YES –| |– NO –|– EXIT –|

Trip query display.

If

YES

(

F1

) is selected, the

TRIP TEST

LED begins to flash.

If

NO

(

F3

) is selected, the

NO TRIP TEST

LED activates. The

next menu lists the available tests:

... ..... ..... ..... ..... ..... ..... ..... .....

Select Test (F4 to EXIT)

|– LT –|– ST –|– GF –|– EXIT –|

Overcurrent test selection menu.

If

ST

(

F2

) or

GF

(

F3

) is selected, the Test Kit first verifies

that the option is installed in the Trip Unit. If that option
is not installed, the appropriate message is displayed, as
illustrated above in the Short Time and Ground Fault
settings tests.

Long Time Test

If

LT

(

F1

) is selected, the Test Kit displays the message:

... ..... ..... ..... ..... ..... ..... ..... ..... ..

Set Current Setting and press F3

|– CONT –|– EXIT –|

Long Time current setting display.

Select the desired current setting on the Trip Unit, then
press

CONT

(

F3

), which displays the verification message:

... ..... ..... ..... ..... ..... ..... ..... ..... ....

LONG TIME TEST WITHOUT BREAKER TRIP

|– CONT –|– EXIT –|

Long Time test verification display.

Press

CONT

(

F3

) to initiate the test or

EXIT

(

F4

) to return

to the function test menu.

Short Time Test

If

ST

(

F2

) is selected from the overcurrent test selection

menu, the Test Kit displays the message: