TVRMS2 Digital Test Kit

Chapter 5. MicroVersaTrip Plus™ and MicroVersaTrip PM™ Trip Units

15

5–1 Test Structure (MicroVersaTrip

Plus™ and MicroVersaTrip PM™)

Figure 11 shows the test-selection structure for Micro-
VersaTrip Plus and MicroVersaTrip PM Trip Units. Each
test sequence is described in detail below.

If an A, B, C, or TT Trip Unit or Spectra breaker is
selected, the Test Kit immediately displays the main test-
selection menu:

... ..... ..... ..

Press F1,F2, or F3 for test selection

|FUNCTION |HICURRENT| QUICK |

Main test-selection menu.

With some versions of A, B, or C type Trip Units, the Test
Kit displays the following menu:

... ..... .....

Is the GF option included?

|- YES -| |- NO -|– EXIT –|

Ground Fault option query menu.

If the Ground Fault option is included in the Trip Unit,
press

YES

(

F1

). Otherwise, press

NO

(

F3

) to go to the main

test selection menu. Press

EXIT

(

F4

) at any time to return

to the Trip Unit selection menu.

Selecting

FUNCTION

(

F1

)

from the main test-selection

menu displays the Trip Units tests menu:

. . ... . . ... . .. .. .. ..... ... ....

Press F1 or F3 (F4 to EXIT)

|TRIP TEST| |SELF TEST|– EXIT –|

Trip Units tests menu.

Trip Test mode is described in section 5-3 Overcurrent
Simulation

and Self-Test is described in section 5-2 Self-Test

Report

. Press

EXIT

(

F4

) to return to the function test menu.

Test Selection

High-Current

Tests

Quick

Test

Function

Tests

Trip

Breaker

GF Defeat

and Monitor

Self-

Tests

Overcurrent

Tests

Trip

Tests

No-Trip

Tests

LT

ST

GF

LT

ST

GF

Trip Unit

Status Report

Enter Settings

LT

ST

GF

Figure 11. Test-selection structure for MicroVersaTrip Plus™ and MicroVersaTrip PM™ Trip Units.