3 messages list, Messages list – GE Industrial Solutions SG Series 750 T12 UL S2 User Manual User Manual

Page 33

Advertising
background image

Modifications reserved

Page 33/71

OPM_SGS_USM_M75_M75_2US_V010.doc

User Manual SG Series 750 UL S2 & SG Series 750 T12 UL S2

6.3.3 Messages list

Code

Message

Meaning

4002

WATCHDOG RESET

The microprocessor has detected an incorrect operation:
Transfers the Load on Utility and performs a program
reset.
The Inverter will restart automatically and will supply the
Load.

4108

Q4 OPEN

The auxiliary contact indicates that the input rectifier
switch Q4
has been opened.

4108

Q4 CLOSED

The auxiliary contact indicates that the input rectifier
switch Q4
has been closed.

4111

RECTIFIER UTILITY OK

Rectifier Input Utility is again within the admitted tolerance
(voltage, frequency and phase).

4119

BATTERY TEST STARTED

Start of Manual or Automatic Battery Test.

4120

BATTERY TEST STOPPED

End of Manual or Automatic Battery Test.

4122

MANUAL BOOST CHARGE ON

Start of Manual Boost charge (only for lead open wet
batteries).

4123

AUTOMATIC BOOST CHARGE

ON

Start of Automatic Boost charge (only for lead open wet
batteries).

4124

BOOST CHARGE OFF

End of Manual or Automatic Boost charge (only for lead
open wet batteries).

4161

RECTIFIER ON

Rectifier started.

4162

RECTIFIER OFF

Rectifier shutdown.

4163

GENERATOR ON

Customer Interface Board (X1 - 11, 22) received a Gen-set
ON
signal.
Operating mode depend on setting of Parameters.

4164

GENERATOR OFF

Customer Interface Board (X1 - 11, 22) received a Gen-set
OFF
signal.
Function Bypass enabled depends on setting of parameter.

4302

INVERTER CANNOT BE TURNED

ON

Inverter cannot be switched on because one of the
following conditions is still present:
- Over Temperature -

K7 opening Failure

- Low Battery Voltage

- High Battery Voltage

- Inverter Fuses

- DC Low

- Overload

- EPO

4303

INVERTER CANNOT BE TURNED

OFF

Inverter cannot be switched OFF, because the Load cannot
be switched to Utility (voltage out of tolerance, not
synchrony, BP blocked).

4361

INVERTER ON

The command to start the Inverter has been activated on
the control panel.

4362

INVERTER OFF

The command to switch OFF the Inverter has been
activated by the control panel or automatically for alarm
presence.

4411

BYPASS UTILITY OK

Bypass Input Utility is again within tolerance (voltage,
frequency and phase).

4500

COMMAND LOAD OFF

Disconnection of the Load by opening K6 and K7 for:
EPO / Load Off / Overload / Stop Operation.

4521

NO BYPASS POWER

With the Load supplied by Automatic Bypass, a Utility
Failure
or K6 opening occurred.