GE Industrial Solutions SG Series 750 T12 UL S2 User Manual User Manual

Page 34

Advertising
background image

Modifications reserved

Page 34/71

OPM_SGS_USM_M75_M75_2US_V010.doc

User Manual SG Series 750 UL S2 & SG Series 750 T12 UL S2

Code

Message

Meaning

4534

MULTIPLE LOAD TRANSFER

2 transfers Inverter- Utility have been detected in a short
time, (default 30 seconds).

4535

BYPASS LOCKED

Bypass is not available.
Contactor K6 is open, SSM deactivated.

4536

BYPASS FREE

Bypass is enabled.
Contactor K6 is closed.

4561

LOAD OFF

The “Load Off” key on the UPS Control Panel has been
pressed, with the output circuit switch Q1 closed.

4562

DETOUR ON

The auxiliary contact indicates that External Maintenance
Bypass
has been closed.

4564

DETOUR OFF

The auxiliary contact indicates that External Maintenance
Bypass
was opened.

4567

COMMAND LOAD ON UTILITY

The control unit received a command to transfer the Load
on Utility.

4568

COMMAND LOAD ON INVERTER

The control unit received a command to transfer the Load
on Inverter.

4572

NO MORE OVERLOAD

End of the overload condition detected with alarm 4570.

4580

INVERTER AND UTILITY

SYNCHRONIZED

The voltages of Inverter and Utility Bypass are
synchronized.

4582

COMMAND NOT TO

SYNCHRONIZE

Command not to synchronize with Utility.

4583

COMMAND TO SYNCHRONIZE

Command to synchronize with Utility.

4600

COMMAND UPS ON

The eBoost™ Operation Mode has been disabled or the
programmed time is expired.
The UPS returns to VFI Operation Mode supplying the Load
normally by Inverter.

4601

COMMAND UPS STANDBY

The eBoost™ Operation Mode is enabled, and according to
the time program the UPS will run in eBoost™ Operation
Mode
, supplying the Load normally by Utility.

4602

Q1 OPEN

The auxiliary contact indicates that the output switch Q1
has been opened.

4603

Q1 CLOSED

The auxiliary contact indicates that the output switch Q1
has been closed.

4604

COMMAND IEMi ON

The IEMi Operation Mode function is enabled, and
according to the time program the UPS system will run in
IEMi mode.
The UPS returns to VFI Operation Mode supplying the Load
normally by Inverter.

4605

COMMAND IEMi OFF

The IEMi Operation Mode has been disabled or the
programmed time is expired.

4606

eBoost ACTIVATION ALLOWED

eBoost/IEMi control signal has been cleared on the
Customer Interface Board (X1 - 11, 22).
Operating mode depends on scheduled activation of the
functions.

4607

eBoost ACTIVATION INHIBITED

Customer Interface Board (X1 - 11, 22) received an
eBoost/IEMi control signal.
eBoost™ Operation Mode and IEMi Operation Mode will be
temporarily inhibited.




Advertising