User Manual SG Series 750 UL S2 & SG Series 750 T12 UL S2

Code

Message

Meaning

4699

BATTERY TEST IMPOSSIBLE

Automatic Battery Test is not possible due to:

No Utility Rectifier or Bypass.

Battery not fully charged.

Load is below 10% or above 80%.

Test is postponed for 1 week.

4763

REMOTE CONTROL ON

Inverter can be started or shutdown by remote control.
Commands source can be chosen depending on the value
of parameter (Service only):
0 = Only

Local

Panel.

1 = Only

Remote

Control.

2 = Both.

4764

REMOTE CONTROL OFF

Inverter cannot be started or shutdown by remote control.
Commands source can be chosen depending on the value
of parameter (Service only):
0 = Only

Local

Panel.

1 = Only

Remote

Control.

2 = Both.