User Manual SG Series 750 UL S2 & SG Series 750 T12 UL S2

`

Home\Setup\User

DISPLAY

UPS name

:

SG Series

Language :

ENGLISH

Contrast

V

LCD Display screen

UPS Name

The user can choose the name of the UPS
model shown on the main page (max. 9

characters).

Language

This parameter allows the choice of
language used to display the information.
Valid choices are: English, German, Italian,

Spanish, French, Finnish, Polish, Portuguese,

Czech, Slovakian, Chinese, Swedish, Russian

and Dutch.

Contrast This parameter controls the contrast of the LCD screen in ten steps (0 – 9).


`

Home\Setup\User

eBoost

Enabled :

N

DAY OF WEEK

d1 d2

d3

d4

d5

d6

d7

HOURS / DAY

24 24 12 12 12 12 12

eBoost™ Operation Mode screen (option)

This screen is displayed only when eBoost™ Operation

Mode is available (option).

Enabled (Y / N / Wait)

Y/N

This parameter (values Y/N) enables or disables the
eBoost™ Operation Mode.

If the value is Y and the current time is in the interval
for the current day, the eBoost™ Operation Mode is
active.

Wait The eBoost™ Operation Mode configuration is being

updated.

In case of Parallel System
If eBoost™ Operation Mode is currently disabled (N) and Q1 is closed, when programming it to enable
(Y) the selected configuration will automatically be propagated to all units in the parallel system.

The activation / deactivation of eBoost™ Operation Mode is indicated each time in the event list.

In order to check the inverter function, at least 1 minute of VFI Operation Mode must be programmed during the
week (the Y/N parameter is automatically disabled if this condition is not satisfied).
In case this minimum time in VFI Operation Mode is not respected, the eBoost™ Operation Mode will be disabled.

If the value is N, the UPS is normally operating in VFI / double conversion mode at all times.

Status of the Home Page with UPS
functioning in eBoost™ Operation Mode.

DAY OF WEEK (d1 ÷ d7):

Enabling time in function of weekdays

Note:

the configuration of the activation schedule can only be

updated when eBoost™ Operation Mode is disabled (Enabled: N).

For the weekdays from d1 to d7 (Saturday to Friday) the edit mode (edit
day) allows to define time intervals when the UPS is operating in
eBoost™ Operation Mode. The hour is given in 24-hour format.

These intervals are defined by:

eBoost START:

The hour of the day after which the eBoost™ Operation Mode is enabled.

The eBoost™ Operation Mode is enabled until the following eBoost STOP time is reached (the eBoost STOP time of

the same day if this is later than the eBoost START time, the eBoost STOP time of the following day otherwise).

eBoost STOP:

The hour of the day before which the eBoost™ Operation Mode is enabled.

The eBoost™ Operation Mode is enabled starting from the preceding eBoost START time (the eBoost START time of
the same day if this is earlier than the eBoost STOP time, the eBoost START time of the previous day otherwise).

Identical times for eBoost START and eBoost STOP maintain the existing mode only in case the previous command
was eBoost START and the following command will be eBoost STOP.

HOURS / DAY:

The number of eBoost™ Operation Mode hours per weekday (from d1 - Saturday to d7 - Friday) is displayed in the
operation mode parameter window (ceiling value).