4 complete ups shutdown, Complete ups shutdown – GE Industrial Solutions SG Series 750 T12 UL S2 User Manual User Manual

Page 51

Advertising
background image

Modifications reserved

Page 51/71

OPM_SGS_USM_M75_M75_2US_V010.doc

User Manual SG Series 750 UL S2 & SG Series 750 T12 UL S2

7.1.4 Complete UPS shutdown

NOTE !

Follow this procedure only in case the UPS system and the Load must be completely
powered-down.
If eBoost™
option is available, make sure that eBoost™ Operation mode is disabled
before starting this procedure.


Initial status:

Load supplied from Inverter.

1. Press

Load Off key.

Load is disconnected from UPS.
Rectifier and Inverter are shut down, all output

and input Contactors will be opened.
LED 3 (Rectifier ON), LED 5 (Inverter available) and

LED 9 (Load on UPS) are OFF.
LED’s, Rectifier, Inverter and Load are OFF.

The Battery remains connected to the UPS in case of configuration without External
Battery Breaker
!

2. Open the UPS Output Switch Q1 (Pos. O).

3.

Disconnect the Battery from the UPS (only for UPS configuration without External Battery
Breaker).

`

Home\Meter

BATTERY

V

15 V

I

5.0 A

T

+25° C

Charge level

80 %

Autonomy

12 Min

Wait a minimum of 5 minutes for DC-Link
Capacitors
to discharge.

Before you proceed with any kind of intervention on
the UPS, make sure the DC-Link voltage
be less than
15 VDC.

4. Disconnect the Utility from the input distribution.

• Complete power shutdown will OFF the LCD Display

Panel.

END OF PROCEDURE