4.6 CONTROL BUS CABLES CONNECTION

WARNING !

The installation and connection must be performed by QUALIFIED SERVICE
PERSONNEL only.
Refer to the “Safety prescriptions - Installation
” described on page 6.


Carefully read the following recommendations before proceeding:

Ensure that the AC external isolators are Off, and prevent their in adverted operation.

Do not close any external isolators prior to the commissioning of the equipment.

The input / output cables must be put in order and fixed, taking care to avoid risk of short-circuit
between different poles.

The earthing connection of the electrical system must be in accordance with local regulations.

Fig. 4.6-1 Diagram showing the maximum allowable length of communication cables

The standard length of the control
bus cable between ISM and the
first unit of each group is 12 m / 40
ft
.

Maximum distance between ISM
and the last unit of each group is
85 m / 279 ft.

L max. :

85 m – [(No. of UPS – 1) x 12 m]

279 ft – [(No. of UPS – 1) x 40 ft]

Maximal number of UPSs in one
group is 6.


ISM_L

B

S_C

B

C

c

onnec

ti

on_01G

B

P6

P5

J52

J53

J63

J62

JA

2

JA

1

JB

2

JB

1

JB

1

JB

2

JA

1

JA

2

Control bus cables

Group A

Control bus cables

Group B

Fig. 4.6-2 Connection of the cables of the communication

bus to P5 / P6 – Parallel bus interface

Control bus cables
Group B

Control bus cables

Group A

IS

M

_

L

BS_

CBC

c

onnec

tion

_02GB

Fig. 4.6-3 Internal connection of the communication bus cables