GE Industrial Solutions ISM User Manual

Page 22

Advertising
background image

Modifications reserved

Page 22/34

OPM_ISM_OPT_10K_M50_0GB_V021.doc

Operating Manual ISM – Intelligent Synchronization Module

MAINTENANCE

MAINTENANCE

LOAD

BYPASS

INVERTER

BYPASS

INVERTER

GROUP B

GROUP A

BYPASS OK

INVERTER OK

B SYNC TO A

A SYNC TO B

INVERTER OK

BYPASS OK

STS

SYNC MASTER

A

B

ISM_LBS_CP 2_01

Fig. 5.2-2 Control Panel – Part 2

A

B

SYNC MASTER A (B) – Green LED
Pushbuttons commands:
A When

pressed,

Group A will be the synchronization “Super Master” and Group

B will synchronize to Group A.
The “SYNC MASTER A” LED will be lit.
Pressing this button disables the automatic “Super Master” selection.

B When

pressed,

Group B will be the synchronization “Super Master” and Group

A will synchronize to Group B.
The “SYNC MASTER B” LED will be lit.
Pressing this button disables the automatic “Super Master” selection.

The SYNC MASTER A (B) green LED, indicates whether Group
A or B is the Super Master.

OUTPUT SYNC – Green LED
When lit, it indicates that the UPS outputs of Groups A and B are synchronized
and within the allowed limits.
This indication is derived from comparing the output of the second UPS group to
the output of the selected “Super Master” group.
When blinking, it indicates that the UPS outputs of Groups A and B are
synchronizing.

MAINTENANCE

BYPASS

INVERTER

OUTPUT – Green LED
The corresponding LED will be lit, depending on the UPS output status of Group A
(or B): INVERTER, BYPASS (Automatic Bypass) or MAINTENANCE (Manual Bypass).

INVERTER OK

INVERTER OK – Green LED
When lit it indicates that the inverter power to UPS Group A (or B) is available and it
is within the allowed tolerance.

BYPASS OK

BYPASS OK – Green LED
When lit, it indicates that the bypass power to UPS Group A (or B) is available and it
is within the allowed tolerance.

A SYNC TO B

A SYNC TO B – Green LED
When lit, it indicates that the UPS outputs of Groups A and B are synchronized and
within the allowed limits. Group B is the synchronization Super Master.

B SYNC TO A

B SYNC TO A – Green LED
When lit, it indicates that the UPS outputs of Groups A and B are synchronized and
within the allowed limits. Group A is the synchronization Super Master.

Advertising