GE Industrial Solutions ISM User Manual

Page 28

Advertising
background image

Modifications reserved

Page 28/34

OPM_ISM_OPT_10K_M50_0GB_V021.doc

Operating Manual ISM – Intelligent Synchronization Module

6.2.1.2 Messages

list

Code

Message

Meaning

4576

SYNCHRONIZE

TO GROUP A

The command for the synchronization of Group A and B is active
and Group A was chosen to be the Super Master.

4577

SYNCHRONIZE

TO GROUP B

The command for the synchronization of Group A and B is active
and Group B was chosen to be the Super Master.

4578

GROUP A AND B
SYNCHRONIZED

The command for the synchronization of Group A and B is active
and the phase error measured between the inverters of Group A
and B stays below the value specified in the respective
parameter.

4582

COMMAND NOT TO

SYNCHRONIZE

ISM disabled the synchronization between Group A and B,
because the either key SYNC OFF was pressed or missing
communication was detected.

4583

COMMAND TO
SYNCHRONIZE

ISM enabled the synchronization between Group A and B,
because either the key SYNC AUTO or one of the keys SYNC
MASTER A
or SYNC MASTER B was pressed.



Advertising