1 metering mode – GE Industrial Solutions ISM User Manual

Page 25

Advertising
background image

Modifications reserved

Page 25/34

OPM_ISM_OPT_10K_M50_0GB_V021.doc

Operating Manual ISM – Intelligent Synchronization Module

6.1 METERING

MODE

The metering mode is entered any time when the metering button is pressed.
While in this mode the LCD will display a series of screens containing metering information.

In this mode the buttons perform the following functions:
METERING

Scrolls forward to the next screen.

ALARMS Abandons

the

metering mode and enters the alarms mode.

PARAMETERS Abandons

the

metering mode and enters the parameters mode.

+

Scrolls forward to the next screen.

Scrolls backward to the previous screen.

ENTER

Displays the main screen for this mode.

INTELL. SYNC MODULE

A sync to B

A: LOAD ON INVERTER

B: LOAD OFF

PARAMETERS

METERING

ALARMS

ENTER

-

+

This screen displays the current status of the synchronization command and the UPS outputs (for both
Group A and B).
The information offered by this screen consists of:
Synchronization: The status of the synchronization command (A sync to B, B sync to A or Sync

OFF).

Group A:

The source of the power supplied to the Load (LOAD ON INVERTER, LOAD ON
BYPASS, LOAD ON MAN. BYP. or LOAD OFF).

Group B:

The source of the power supplied to the Load (LOAD ON INVERTER, LOAD ON
BYPASS, LOAD ON MAN. BYP. or LOAD OFF).

OUTPUT STATUS

Synchronized

Load A = 50%

Load B = 20%

PARAMETERS

METERING

ALARMS

ENTER

-

+

This screen displays the load of UPSs output (for both Group A and B).
The information offered by this screen consists of:
• Synchronization status between UPSs of Group A and B;
• The load amount as a percentage of the nominal load of Group A (referred to the most loaded

phase);

• The load amount as a percentage of the nominal load of Group B (referred to the most loaded

phase).

MISCELLANEOUS

ISMOperTime

:

123451h

SW Version

:

XXX-YYY

S/N:

72-97756

PARAMETERS

METERING

ALARMS

ENTER

-

+

This screen displays miscellaneous information.
The information offered by this screen consists of:
• The total operating time of the ISM (in hours).
• The software version.
• The serial number.

Advertising