Group a group b, Control bus cables routing – GE Industrial Solutions ISM User Manual

Page 19

Advertising
background image

Modifications reserved

Page 19/34

OPM_ISM_OPT_10K_M50_0GB_V021.doc

Operating Manual ISM – Intelligent Synchronization Module

IS

M_

LB

S

_

C

B

C

c

o

nn

ec

ti

on_03G

B

UPS 3

UPS 2

Q1

Q2

OF

F

ON

ON

OF
F

Q2

OF

F

ON

OF
F

ON

Q1

UPS 1

OF

F

OF
F

Q2

ON

ON

Q1

UPS 1

UPS 3

UPS 2

Q2

Q2

ON

OF
F

ON

Q1

OF
F

Q2

ON

OF
F

Q1

OF
F

ON

OF

F

ON

Q1

OF
F

ON

P5

P6

GROUP A

GROUP B

Fig. 4.6-1/2

ISM

From ISM to UPS 1 / Group A

Control bus cables Group A

Control bus cables Group B

(from ISM to UPS 1 / Group B)

See Fig. 4.6-5/6

See Fig. 4.6-5/6

Fig. 4.6-4 Connection of the communication bus cables from ISM to UPS’s Group A and Group B

Control bus cables routing

Place and fix the cables JA and JB with the appropriate clamps inside the UPS cabinets.
Pay attention to the fact, that routing of cables shall allow the removal of the protection covers.

NOTE !

Pay attention when cabling and routing the bus cables JA and JB inside the UPS
cabinet.
In case the unit should be removed from the system, the control bus cables Group A
and Group B must be removed from the cabinet without disconnecting them from
the metal plates where are located the sockets JA
and JB. Please contact your
Service Centre.

For reliability reasons the cables JA and JB connecting the units should be run in separated
protected conduits, as well as separated from the power cables.
It is important that the cable JA is as long as cable JB.

ISM_LBS_RPA-IM0048_01

JP3

JP1

JP4

IM 0048

JP2

JP1

JP2

JP4

JP3

JB1

JA1

JB

JA

Fig. 4.6-5 PCB “P34 – Parallel Bus Interface” of UPS number 1 of either

Group A or B, prior to the connection with ISM

JP2

JP1

JP3

JP4

JP3

JP2

JP1

JP4

IM 0048

Control Bus cable from ISM

Control Bus cable from ISM

ISM_LBS_RPA-IM0048_02GB

JA

JB

JB

JA

Fig. 4.6-6 PCB “P34 – Parallel Bus Interface” of UPS number 1 of

either Group A or B, after the connection with ISM

The Jumpers JP1, JP2, JP3 and JP4 ARE
INSERTED
.

The Jumpers JP1, JP2, JP3 and JP4 MUST BE
REMOVED
.

NOTE !

Since the position of PC Board “P34 – Parallel Bus Interface” inside the UPS changes
between the various UPS output powers, it’s recommended to consult the
appropriate Operating Manual
for cable connections.